2231V104-UK 9
AC current input:
Measurement range ................................................ 0...1 ARMS
Min. measurement range (span) ........................ 0.5 ARMS
Max. offset ................................................................. 50% of selected max. value
Input resistance........................................................ 1 Ω / 2 W
Updating time ........................................................... 100 ms
Voltage input:
DC voltage input:
Measurement range ................................................ 0...250 VDC
Min. measurement range (span) ........................ 0.5 VDC
Max. offset ................................................................. 50% of selected max. value
Input resistance........................................................ Nom. 5 MΩ
Updating time ........................................................... 100 ms
AC voltage input:
Measurement range ................................................ 0...250 VRMS
Min. measurement range (span) ........................ 0.5 VRMS
Max. offset ................................................................. 50% of selected max. value
Input resistance........................................................ Nom. 5 MΩ
Updating time ........................................................... 100 ms
Electrical specifications - OUTPUT :
Relay outputs:
Setpoint setting ....................................................... 0...99.9% of span
Hysteresis ................................................................... 0...99.9% of span
Updating time ........................................................... 100 ms
Delay ............................................................................. 0.0...99.9 s
Max. voltage .............................................................. 250 VRMS
Max. current ............................................................... 2 A / AC
Max. AC power .......................................................... 500 VA
Max. load at 24 VDC ............................................... 1 A
Marine approval:
Det Norske Veritas, Ships & Offshore ............. Standard for Certification No. 2.4
Observed authority requirements: Standard:
EMC 2004/108/EC .................................................. EN 61326-1
LVD 2006/95/EC ...................................................... EN 61010-1
PELV/SELV .................................................................. IEC 364-4-41 and EN 60742
EAC TR-CU 020/2011 ............................................ EN 61326-1
Of span = Of the presently selected range