001 = Single setpoint:
Single trip amplifier set in main menu 1.0 with setpoint within the range
0...99.9% of the input signal. The hysteresis is set in the range 0...99.9%
of the input signal. The parameter selection
determines whether the trip amplifier should be active for increasing
(InC) or decreasing (dEC) input signal. The delay time is set in the range
0...99.9 s. Settings in main menu 2.0 rE2 are of no importance as relay
2 is disconnected.
002 = Dual setpoint:
Dual trip amplifier with setpoint on both relays within the range 0...99.9%
of the input signal. The hysteresis is set in the range 0...99.9% of the input
signal. The parameter selection determines whether the trip amplifiers
should be active for increasing (InC) or decreasing (dEC) input signal. The
time delay is set in the range 0...99.9 s. Relay 1 is set in main menu 1.0
rE1; relay 2 is set in main menu 2.0 rE2.
003 = Pre-setpoint:
Dual trip amplifier with setpoint on relay 1 within the range 0...99.9% of
the input signal and a percentage pre-setpoint on relay 2. On relay 1, the
hysteresis is set in the range 0...99.9% of the input signal.
The parameter selection in menu 1.3 InC increasing / dEC decreasing
input signal is disconnected, as the pre-setpoint function acts on an
increasing (InC) input signal. The time delay is set in the range 0...99.9 s.
The relay 2 pre-setpoint is entered in submenu 2.1 as the percentage
value by which relay 2 is activated before relay 1, and in submenu 2.2 the
percentage hysteresis of the pre-setpoint is entered. In submenus 2.1 and
2.2, settings of 5 and 0.5 respectively will mean that relay 2 is activated
5% earlier than relay 1 and that there will be a hysteresis of 0.5%. In main
menu 2.0, the submenus 2.3 and 2.5 are disconnected.
004 = Setpoint window:
Dual trip amplifier with setpoint window on both relays acc. to your
choice. The setpoint window is set with a low and an upper value on
the input signal thus making the relays active / inactive within the range.
In submenus 1.1 / 2.1 the low percentage value of the input signal is
set, and in submenus 1.2 / 2.2 the high percentage value of the input
signal is set.