Prosense SCU-2501 - User Manual

Default Icon
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
~ WARNING ~
This device is designed for connection to hazardous electric voltages. Ignoring this warning can result
in severe personal injury or mechanical damage. To avoid the risk of electric shock and fire, the safety
instructions of this guide must be observed and the guidelines followed. The specifications must not be
exceeded, and the device must only be applied as described in the following. Prior to the commissioning
of the device, this installation guide must be examined carefully. Only qualified personnel (technicians)
should install this device. If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Until the device is mounted, do not connect hazardous voltages to the device. The following operations
should only be carried out on a disconnected device and under ESD safe conditions: General mounting,
connection and disconnection of wires.
Do not open the front plate of the device as this will cause damage to the connector for the
display / programming front SCU-PDM2. This device contains no DIP-switches or jumpers. Units must
be mounted on a DIN rail according to DIN 60715
SAFETY INSTRUCTIONS
Receipt and unpacking
Unpack the device without damaging it. The packing should always follow the device until it has been perma-
nently mounted. Check at the receipt of the device to ensure the type corresponds to the one ordered.
Environment
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well as rain and heavy
moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by
way of ventilation. All devices can be used for Measurement / Overvoltage Category II and Pollution Degree
2. The module is designed to operate safely at an altitude of 2000m or less.
Mounting
Mounting and connection of the device should comply with national legislation for mounting of electric
materials, i.e. wire cross section, protective fuse, and location. Descriptions of input / output and supply
connections are shown in this installation guide and on the side label. The following apply to hazardous
voltage-connected devices:
The max. protective fuse is 10A. A power switch shall be easily accessible and close to the device. The power
switch shall be marked as the disconnecting unit for the device.
UL installation requirements
Use 60/75°C copper conductors only.
For use only in pollution degree 2 or better.
Max. ambient temperature ................................................. 60°C (140°F)
Wire size ............................................................................ AWG 26-14
UL file number, SCU-2501, SCU-2502 & SCU-2503....... E197592
The device is an Open Type Listed Process Control Equipment. To prevent injury resulting from accessibility
to live parts the equipment must be installed in an enclosure.
Calibration and adjustment
During calibration and adjustment, the measuring and connection of external voltages must be carried out
according to the specifications of this installation guide. The technician must use tools and instruments that
are safe to use.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
Technical Specifications
Copyright 2022, Automationdirect.com®
Incorporated All Rights Reserved
3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860
Quick Start Guide
Quick Start Guide
Quick Start Guid
eQuick Start Guide
Quick Start Guid
e
Universal Signal Conditioners
ProSense Universal Transmitter Signal Conditioner models SCU-2501,
SCU-2502 and SCU-2503 are single input devices that accept PNP, NPN,
TTL, NAMUR, and custom special trigger current or voltage level frequency.
The SCU-2501 and SCU-2502 models support relay output with the
SCU-2502 having two independently triggered relay outputs. The SCU-2501
and SCU-2503 provide a mA (sourcing or sinking) or voltage output. The
SCU-2503 is the only unit with a frequency output allowing for frequency/
frequency conversion. They feature a plastic slim-line housing, integral 35mm
DIN rail mounting adapter, and removable screw terminals. The detachable
SCU-PDM2 programming / display module (purchased separately) is required
for unit configuration. The programming / display module may remain affixed
for operational display of input and output values.
Models:
SCU-2501 - Universal Frequency Transmitter with Analog and
Relay Outputs
SCU-2502 - Universal Frequency Transmitter with (2) Relay
Outputs
SCU-2503 - Universal Frequency Transmitter with Analog and
Frequency Outputs
Operating temperature .............................. - 20°C to +60°C (-4°F to 140°F)
Storage temperature .................................. -20°C to +85°C (-4°F to 185°F)
Supply voltage............................................ 21.6...253 VAC or 19.2...300 VDC
Max. required power:
SCU-2501/2/3.................................................. 2.6 W
Max. power dissipation:
SCU-2501/2/3.................................................. 2.1 W
Fuse ........................................................... 400mA SB / 250VAC
Isolation voltage, test / operation................ 2.3 kVAC / 250VAC
(reinforced isolation)
EMC immunity influence........................... < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst.......... < ±1% of span
Relative humidity........................................ < 95% RH (non-cond.)
Dimensions (HxWxD) ............................... 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ SCU-PDM2...... 109 x 23.5 x 116 mm
Protection degree ........................................ IP20
Approvals
UL, Standard for Safety .............................. UL 508/C22.2 No. 14
Observed authority requirements:
EMC ........................................................... 2014/30/EU
LVD ............................................................ 2014/35/EU
RoHS 2........................................................ 2011/65/EU
Model SCU-2501 SCU-2502 SCU-2503
Input
Frequency
input
Frequency Range 0.001 Hz to 100 kHz
Time range, time function 10 µs to 999.9 s
Max. frequency, with input filter ON 75Hz
Min. pulse width with input filter ON 8ms
Min. pulse width with input filter OFF 4µs
Response time (0...90%, 100...10%) < 30ms
NAMUR input
Trig-level LOW 1.2 mA
Trig-level HIGH 2.1 mA
Input impedance 1 kΩ || < 220pF
Breakage detection 0.1 mA
Short-circuit detection 6.9 mA
Sensor supply - pin 44, fixed 8.3 V
Tacho input
Trig-level LOW -50 mV
Trig-level HIGH +50 mV
Input impedance 100 kΩ || < 220 pF
Max. input voltage 80VAC pp
Sensor supply - pin 44,
programmable
5...17 V / 23mA
NPN / PNP
input
Trig-level LOW 4.0 V
Trig-level HIGH 7.0 V
Input impedance 3.48 kΩ || < 220 pF
Trigger edge NPN = Neg. edge, PNP = Pos. edge.
Sensor supply - pin 44,
programmable
5...17 V / 23mA
TTL input
Trig-level LOW 0.8 V
Trig-level HIGH 2.0 V
Input impedance 100 kΩ || < 220 pF
Sensor supply - pin 44,
programmable
5...17 V / 23mA
S0 input
Trig-level LOW 2.2 mA
Trig-level HIGH 9.0 mA
Input impedance 758 Ω || < 220 pF
Sensor supply - pin 44, fixed. 17V
Special
voltage input
User-programmable trig-levels -0.05...6.50 V
*Hysteresis, min 50 mV
Input impedance, programmable:
High Z: 100 kΩ || < 220 pF
Pull up/down; 3.48 kΩ || < 220 pF
Programmable sensor supply - pin 44 5...17 V / 23 mA
Max. input voltage 17V
Special
current input
User-programmable trig-levels. 0.0...10.0 mA
*Hysteresis, min 0.2 mA
Input impedance 1 kΩ || < 220 pF
Sensor supply - pin 44,
programmable
5...17 V / 23 mA
Max. input current 17mA
Model SCU-2501 SCU-2502 SCU-2503
Output
Current output
0...20, 4...20, S4-20,
±10 mA, ±20 mA
----------
0...20, 4...20, S4-20,
±10 mA, ±20 mA
Load (max.), current output 600 Ω ---------- 600 Ω
Current limit 28 mA ---------- 28 mA
Voltage output
0…5, 1…5, 0...10,
2…10, ±5, ±10 VDC
----------
0…5, 1…5, 0...10,
2…10, ±5, ±10 VDC
Load (min.), voltage output 2 kΩ ---------- 2 kΩ
Relay output
SPST, AC: 250 VAC/
VDC, 2A, 500VA
2 x SPST, AC: 250
VAC/VDC, 2A, 500VA
----------
Frequency output
---------- ---------- 0.001 Hz...100kHz
PNP output
---------- ----------
24VDC at 30mA
max
NPN output
---------- ----------
30VDC at 130mA
max
Push-Pull output
---------- ---------- 5...24VDC
* For low signal levels with input trigger level hysteresis below 100 mV / 0.1 mA it is
recommended to use shielded cables with correct grounding, to avoid false triggering due to
induced EMC.
Side Label
Note: Additional specifications available at www.AutomationDirect.com
Question and Answer IconNeed help?

Do you have a question about the Prosense SCU-2501 and is the answer not in the manual?

Overview

The ProSense SCU-2501, SCU-2502, and SCU-2503 are universal frequency transmitters designed to convert various input signals into a scalable analog output or act as a frequency relay. The SCU-PDM2 is a programming module used in conjunction with these transmitters.

Function Description

These devices serve as versatile signal conditioners, translating diverse input types into standardized outputs. The SCU-2501 is a universal frequency transmitter with an analog output, while the SCU-2502 is a universal frequency transmitter with an analog output and two relays. The SCU-2503 is a universal frequency transmitter with two relays. They can accept inputs such as special current, special voltage, tachometer, PNP, NPN, contact (NPN), Namur, S0, and TTL signals. The output can be a scalable 4-20mA analog signal or frequency relay outputs. This allows for integration into various control systems, providing flexibility in signal conversion and monitoring. The SCU-PDM2 programming module facilitates configuration and setup of the transmitters.

Important Technical Specifications

The devices operate within a wide ambient temperature range of -20°C to 65°C (-4°F to 149°F) and a storage temperature of -20°C to 70°C (-4°F to 158°F). The maximum relative humidity is 95% non-condensing.

Power Supply:

  • Max. power dissipation: 2.6 W
  • Supply voltage: 21.6 - 250 VAC / 19.2 - 300 VDC
  • Fuse: 500 mA SB / 250 VAC

EMC Immunity Influence:

  • Extended EMC immunity: < 0.1% of span
  • EMC immunity (vibration, burst, radiated, conducted): < 1% of span
  • Dimensions (HxWxD): 109 x 23.5 x 116 mm
  • Dimensions (HxWxD) w/ SCU-PDM2: 109 x 23.5 x 116 mm
  • Protection degree: IP50

Standards and Approvals:

  • UL Standard for Safety: UL 508/C22.2 No. 14
  • EMC immunity requirements: 2014/30/EU
  • LVD: 2014/35/EU
  • RoHS 2: 2011/65/EU

Input Specifications (SCU-2501, SCU-2502, SCU-2503):

  • Frequency Range: 0.001 Hz to 100 kHz
  • Minimum pulse width: 4µs
  • Max. frequency with input filter ON: 75 Hz
  • Min. pulse width with input filter ON: 6.6 ms
  • Max. frequency with input filter OFF: 8 kHz
  • Min. pulse width with input filter OFF: 62.5 µs
  • Trip level low: < 1.2 mA
  • Trip level high: > 1.2 mA
  • NAMUR input (EN 60947-5-6):
    • Breakage detection: < 0.3 mA
    • Short circuit detection: > 6.5 mA
    • Sensor supply: 8.1 V
  • Tacho input:
    • Input impedance: > 100 kΩ
    • Input voltage: > 40 mV
    • Input current: > 100 µA
    • Sensor supply: 5.1 V / 23µA
  • PNP/NPN input:
    • Input impedance: > 100 kΩ
    • Input voltage: > 40 mV
    • Input current: > 100 µA
    • Sensor supply: 5.1 V / 23µA
  • TTL input:
    • Input impedance: > 100 kΩ
    • Input voltage: > 40 mV
    • Input current: > 100 µA
    • Sensor supply: 5.1 V / 23µA
  • S0 input:
    • Input impedance: > 100 kΩ
    • Input voltage: > 40 mV
    • Input current: > 100 µA
    • Sensor supply: 5.1 V / 23µA
  • Special voltage input:
    • Input impedance: > 1 MΩ
    • Input voltage: 0-10 V
    • Input current: 0-10 mA
    • Sensor supply: 5.1 V / 23µA
  • Special current input:
    • Input impedance: 100 Ω
    • Input current: 0-20 mA
    • Sensor supply: 5.1 V / 23µA

Output Specifications (SCU-2501, SCU-2502, SCU-2503):

  • Analog output (SCU-2501, SCU-2502):
    • Current (mA): 0-20 mA, 4-20 mA, 0-10 mA, 2-10 mA, 0-5 mA, 1-5 mA
    • Voltage (V): 0-10 V, 2-10 V, 0-5 V, 1-5 V
    • Load (max.): 500 Ω (current), 10 kΩ (voltage)
  • Relay output (SCU-2502, SCU-2503):
    • Type: SPDT (single pole, double throw)
    • Contact rating: 250 VAC / 2A, 30 VDC / 2A
    • Frequency: 0.001 Hz to 100 kHz
    • Minimum pulse width: 4µs
    • Output frequency: 0.001 Hz to 100 kHz
    • Output current: 0-20 mA
    • Output voltage: 0-10 V
    • Output resistance: 500 Ω
    • Output capacitance: 100 nF
    • Output inductance: 100 µH
    • Output power: 100 W
    • Output voltage (max.): 250 VAC / 30 VDC
    • Output current (max.): 2A

Usage Features

Mounting:

The devices are designed for DIN rail mounting. To mount, place the top notch of the module onto the DIN rail and press the lower portion until it snaps into place. For the SCU-PDM2, insert its tabs into the holes at the top of the device and swing it down until it snaps into place.

Wiring:

The maximum wire size is 1 x 2.5 mm² stranded wire. Screw terminal torque is 0.5 Nm. It is crucial to remove connectors with hazardous voltages before detaching the device from the DIN rail.

Configuration:

The SCU-PDM2 programming module is essential for configuring the transmitters. After mounting the unit on a DIN rail, connecting power, input, and output wires, and snapping on the SCU-PDM2, power up the unit. The unit should display the configuration menu. If not, press OK once.

  • Press OK to begin configuration.
  • Use the UP/DOWN arrows to scroll through options at each step.
  • Press OK to confirm an option and move to the next step.
  • Press and hold OK to step backwards through the configuration menu.
  • If no sensor is connected, a "SE.BR" error will flash. Press OK once to acknowledge and then again to display the menu.
  • Password protection is available for advanced settings, requiring a 4-digit code.

Error Messages and Troubleshooting:

The display flashes error indications once per second. Input loop errors also cause the backlight to flash, which can be acknowledged by pushing the 3 button.

  • IN.ER (Input error): Input out of configured input limits. Check input signal value and configured limits.
  • IN.LO (Input underrange): Input below low cut-off. Check input signal source.
  • IN.HI (Input overrange): Input above valid measurement range. Check input signal source.
  • -1999 or 9999 (Display out of range): Display saturation. Check configuration and input values.
  • AO.ER (Analog output error): Error in analog output current. Check wiring of analog output and recycle power.
  • SE.OL (Sensor supply overloaded): Sensor supply overload detected. Check sensor supply specifications.
  • SE.SH (Sensor short circuit): Sensor short circuit condition. Check sensor for short circuit.
  • SE.BR (Sensor wire break): Sensor open loop/broken wire condition. Check sensor for open loop/broken wire.
  • NO.CO (No communication): No communication between device and SCU-PDM2. Reattach SCU-PDM2 interface.
  • CO.ER (Configuration error): Invalid configuration downloaded to module. Step through menu to create valid configuration.
  • TY.ER (Invalid configuration type or version): Configuration read from SCU-PDM2 has invalid type or rev. no. Save correct device type and revision configuration.
  • AO.SU (Analog output supply error): Analog output supply error. Verify output configuration and connection.
  • RA.ER (RAM error), AD.ER (A/D converter error), IF.ER (Internal flash error), FL.ER (Frequency input error), EE.ER (EEPROM Error): Internal errors. Contact AutomationDirect.
  • CO.WARN (Storing of configuration failed): Writing configuration to internal device memory failed. Device configuration reverts to last known valid configuration. Cycle through menu to retry writing new configuration.

Maintenance Features

Cleaning:

The device can be cleaned with a cloth moistened with distilled water.

Troubleshooting:

The manual provides a comprehensive list of error messages and corresponding actions. Many errors can be resolved by checking wiring, configuration settings, or power cycling the device. Internal errors typically require contacting AutomationDirect. Acknowledging errors is done by pressing the 3 button for input loop errors or by stepping through the basic setup or resetting device power for other errors.

Prosense SCU-2501 Specifications

General IconGeneral
BrandProsense
ModelSCU-2501
CategoryTest Equipment
LanguageEnglish