PRESET VALUES
000.2
Delay at Power Up
000.2
Delay at Power Up
000.2
Delay at Power Up
e 0020
Gen Detect Set-Point
0 005.0
Restore Delay on Overload
0 005.0
Restore Delay on Overload
c 0020
Algorithm Adjustment 2
2 02.0
Preset Not Adjustable
f3 54.0
F3 Under Freq. Setting
f1 58.0
Preset Not Adjustable
1 03.0
F1 Under Freq. Delay
Time
u 0 150
“P” Load Restore Delay
3 00.5
Preset Not Adjustable
y 000.0
Scroll Comp. Saver
g 005.0
Restore Delay on Gen
g 005.0
Restore Delay on Gen
s 020
Algorithm Adjustment 1
f2 56.0
Preset Not Adjustable
2 02.0
F2 Under Freq. Delay
Time
0001
Factory Test Mode
f1 57.5
F1 Under Freq. Setting
p 001.5
O/L On Restore Detect
f3 53.0
Preset Not Adjustable
3 00.5
F3 Under Freq. Delay Time
1 03.0
Preset Not Adjustable
f2 55.0
F2 Under Freq. Setting
h 002
Consecutive B4 Sleep
Mode Menu
Press Mode button 3 sec.
to enter MASTER menu
L
Press Mode button 1
sec. to adjust settings
up
Press Mode button 1
sec. to adjust settings
uA
Press Mode button 1
sec. to adjust settings
FA
Press Mode button 1
sec. to adjust settings
Load Drop
Under Frequency
Preset Values
Under Frequency
Adjustable Values
Factory
Adjustments
L
B 0000
UP
B 0001
C 0001
ua
B 0001
C 0000
FA
Adjust relay program start
up delay at Power-Up from
000.1 to 999.9 minutes to
allow power to stabilize
Adjust relay program start
up delay at Power-Up from
000.1 to 999.9 minutes to
allow power to stabilize
Adjust relay program start
up delay at Power-Up from
000.1 to 999.9 minutes to
allow power to stabilize
Adjust the Sine Wave Distortion Index™
to set generator detect threshold.
Default setting: 0020
Consult technical support
Adjust the delay time in
minutes before restoring
load after under frequency
load drop event
Adjust the delay time in
minutes before restoring
load after under frequency
load drop event
Service Adjustment. Default 020
Consult technical support
Set delay time from
00.01 to 10.00 seconds
for F2 Under Frequency
Load Shed
Under Frequency F3 set
from 50.00 to 60.00 Hz.
follows delay d3
Under Frequency F1
preset from 58.0 Hz.
follows delay d1
Set delay time from
00.01 to 10.00 seconds
for F1 Under Frequency
Load Shed
Upon load restoration, if under
frequency event occurs within “P”
seconds after restoration, this extended
delay “U” is activated and added to
setting “O” normal restore delay
Set delay time from
00.01 to 10.00 seconds
for F3 Under Frequency
Load Shed
Scroll Compressor Mode
Y0000 Mode OFF
Y0001 - 0030 load o for xx
min after detect utility
return
Adjust the delay time in
minutes before restoring
load after generator sine
wave has been detected
Adjust the delay time in
minutes before restoring
load after generator sine
wave has been detected
Service Adjustment. Default 020
Consult technical support
Under Frequency F2
preset to 56.0 Hz.
follows delay d2
Set delay time from
00.01 to 10.00 seconds
for F2 Under Frequency
Load Shed
Factory Test Mode
0000 = OFF 0001 = ON
UP = Relay On Down = Relay O
Real Time AC Freq. Meter
Under Frequency F1 set
from 50.00 to 60.00 Hz.
follows delay d1
Set delay time from 0001 to 0010
seconds for detection of Over-Load
when load is restored. An extended
delay will be executed as set up in “U
Under Frequency F3
preset to 53.0 Hz.
follows delay d3
Set delay time from
00.01 to 10.00 seconds
for F3 Under Frequency
Load Shed
Set delay time from
00.01 to 10.00 seconds
for F1 Under Frequency
Load Shed
Under Frequency F2 set
from 50.00 to 60.00 Hz.
follows delay d2
Repetitive cycles required to conrm
Utility/Generator waveform default set
to 3 cycles
Push MODE button for
3 seconds to return
to MASTER MENU or
wait 7 seconds to save
adjustments and exit menu
To Enter Master Menu
Press and hold mode button for three seconds and release. Press mode button for 1 second intervals to scroll to desired mode, then press mode button again for three
seconds to store selected mode.
To Adjust Settings Within a Mode
After selecting the desired Master Menu, Press mode button for one second to scroll to desired adjustment, then press up and down keys to desired settings. Repeat for
each setting you need to adjust. Value will be stored after 7 seconds of inactivity.
SAK-24
Menu Flow Chart with Default Settings
Mode Menu
Press Mode button 3 sec.
to enter MASTER menu
Push MODE button for
3 seconds to return
to MASTER MENU or
wait 7 seconds to save
adjustments and exit menu
Mode Menu
Press Mode button 3 sec.
to enter MASTER menu
Push MODE button for
3 seconds to return
to MASTER MENU or
wait 7 seconds to save
adjustments and exit menu
Mode Menu
Press Mode button 3 sec.
to enter MASTER menu
Push MODE button for
3 seconds to return
to MASTER MENU or
wait 7 seconds to save
adjustments and exit menu