Wiring must conform to the National Electrical Code and use a fused disconnect switch for control.
Use only copper wire of proper sizing for incoming service; aluminum wiring voids warranty.
Loosen screw, move knob along scale for desired air position, and tighten screw.
Adjust nozzle position using screw E; remove nozzle by loosening connecting pipe F.
Ensure ignition electrode measurements match Figure 22-4 for proper settings.
Adjust first stage damper arm (C) and second stage knurled ring (B) for optimal flame.
Adjust nozzle assembly (C) with screw E; remove by loosening pipe F and disconnecting 2nd stage oil line.
Verify ignition electrode measurements correspond to Figure 22-7.
Check switches, circuit contacts, fuses, motor overloads, flame safeguard, connections, and oil pump.
Verify electrode settings, wiring integrity, and check for cracked porcelain or loose connections.
Troubleshoot ignition transformer, electrodes, leadwires, plug connections, and air flow switch.
Clean scanner lens/sight tube, check amplifier, or adjust fuel/air ratios for stable flame sighting.
Check for defective or incorrect oil nozzle size and verify fuel/air ratio.
Inspect high fire controls, wiring, flame safeguard, hydraulic cylinder, and linkage for binding.
Verify nozzle, oil pressure, damper settings, pump coupling, and linkage for proper operation.
Address white smoke via air/oil ratios; gray/black smoke via nozzle spray, oil pressure, or ratios.
Check nozzle size, pump pressure, coupling, linkage, and suction line for achieving desired input rate.