EasyManua.ls Logo

Radiant DIAGNOCODE SM 20015 - Page 12

Radiant DIAGNOCODE SM 20015
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P.C.B. SM 20015 boiler settings
9
D
10
20
30
40
MANO METRO
9: Mechanical minimum gas pressure setting
The mechanical minimum gas pressure is factory calibrated on all boilers at 17/18 mmH20.
When replacing the gas valve adjust the mechanical minimum pressure as follows:
:
Using a single cut screwdriver turn D screw (fig.1 ) clockwise and tight it ;
To adjust the mechanical minimum, turn D screw (fig.1) counter-clockwise for
two complete turns.
Parameter 10 setting: MINIMUM HEATING OUTPUT SETTING
To check or modify the existing pressure value:
a. insert a manometer into the gas valve pressure point B (fig.1);
b. Put ON / OFF button
1 in OFF position ( );
c. Push pad
6 and simultaneously and keep them pressed;
d. Put ON / OFF button
1 in ON position ( ) and wait until the display shows - ;
e. Release pad
6 and ;
f. Keeping pad
pressed, press pad 6 and select parameter no. ;
g. Release service pad
, press and release service pad ;
h. The display
will show the parameter value to be set or modified;
i. The manometer inserted in the pressure point B (fig. 1) will show the minimum gas pressure;
j. If that value is different than the one stated on the data plate, modify it by pressing pad
6 to increase or pad to decrease gas pressure ;
k. Once the minimum gas pressure has been adjusted, switch the boiler OFF by putting ON / OFF button
1 in OFF position ( );
l. Remove the silicon pipe from the pressure point B (fig.1), close tightly the pressure point screw and make sure there are no gas leaks;
m. Position the ON / OFF button
1 in ON position ( );
Gas valve VK 4105G
P
L
0
1
0
Fig. 1