OM-FX SERIES 11
Service
This piece of equipment uses a R290 Refrigeration system. This equipment has been clearly
marked on the serial tag the type of refrigerant that is being used. There is also a warning
labels stating that the unit contains R290 refrigerant.
No smoking or open ames when servicing this equipment. If needed, use a CO
2
or dry=power
type re extinguisher
Only authorized service technician, certied in R290 system should service this equipment.
MANIFOLD SET
A R134A manifold set can be used for servicing this equipment.
REFRIGERANT RECOVERY
Follow all national and local regulations for R-290 refrigerant recovery.
LEAKING CHECKING AND REPAIR
Leak check an R-290 system the same way you would an R-134a or R-404A system with the
following exceptions.
1. Do not use a Halid leak detector on a R290 system.
2. Electronic leak detector must be designated specically for combustible gas.
Use of a bubble solution or an ultrasonic leak detector are acceptable.
When repairing a leak, it is recommended using oxygen free dry nitrogen with a trace gas not
exceeding 200PSI.
When accessing an R290 system, piercing valves are not to remain on the equipment in
a permanent manner. After charge is recovered, Schrader valves are to be installed on the
process stubs. Proper charge is to be weighed into the system and the system is to be leak
checked afterwards.
The R290 equipment must have red process tubes and other devices through which the
refrigerant is serviced, such as any service port. This color marking must remain on the
equipment. If marking is removed, it must be replace and extend at least 2.5 centimeters (1”)
from the compressor.
CHARGING
Follow the charge amount specied on the data tag. It is recommended to use the shortest
hoses possible to prevent undercharging.
Ensure the system is sealed and leak checked
Evacuate system to a minimum 500 micron
Weigh in correct charge
Leak check the system again
Bleed the refrigerant from the high side hose to the low side hose
Disconnect the hoses
Remove line taps
CAUTION!
COMPONENT PARTS SHALL BE REPLACED
WITH LIKE COMPONENTS. SERVICE WORK
SHALL BE DONE BY FACTORY AUTHORIZED
SERVICE PERSONNEL, SO AS TO MINIMIZE
THE RISK OF POSSIBLE IGNITION DUE TO
INCORRECT PARTS OR IMPROPER SERVICE.