4
A DX2 sensor package consists of two RJ-45 ports and sensors and/or
terminals.
Different DX2 sensor packages have a different number of sensors,
actuators and/or terminals.
Important: A DX2 contact closure sensor does NOT support any
water detection sensor, including Raritan's DPX water sensors --
DPX-WSF
and
DPX-WSC
series.
DX2 series works with Raritan's DPX3 sensor hub 'DPX3-ENVHUB4', but
not
with the DPX sensor hub 'DPX-ENVHUB4'.
With standard network patch cables, you can:
Connect a DX2 sensor to a Raritan or Legrand product with the
"RJ-45" SENSOR port, such as PX3 or Legrand PDU.
Exception: For a Raritan PDU or EMX with an "RJ-12" SENSOR port,
an RJ-12 to RJ-45 adapter cable (part number: RJ12M-RJ45M) is
needed, which you can request from Raritan.
Daisy chain DX2 sensor packages.
Warning: Do NOT use a crossover cable for connection.
In This Chapter
Available DX2 Sensor Packages..................................................................5
DX2-DH2C2 Door Handle Controller...........................................................6
DX2 Temperature and Humidity Sensors ...................................................9
DX2-CC2 Contact Closure Sensors...........................................................11
Cascading DX2 Sensor Packages.............................................................. 17
Chapter 2 DX2 Series