Chapter 3: Using the Web Interface
101
Enable Modbus Access
For details on Modbus, see Configuring Modbus TCP and/or RTU.
To enable Modbus access:
1. Select the power meter or panel in the Power Meters page.
2. Click the actions icon to open the options, then choose Configure.
3. Select the Enable Modbus Access checkbox, and assign a "unique"
Modbus address to the power meter.
This Modbus address must be different from that of the main
controller, any panel or power meter module connected to this
BCM2, or the BCM2 does NOT allow you to save this dialog.
If Modbus/RTU is enabled, make sure this Modbus address is
also different from those of other devices on the same Modbus
RTU bus.
4. Click OK to save.
Viewing the Panel Data
To view panel data, including mains circuit and branch circuits, go to the
Power Meters page and click to select a panel. You can also select a
panel from the dashboard.
The Panel details page opens with a list of sensor data and readings at
the top, and a list of Panel Branch Circuits at the bottom.