Chapter 3: Using the Web Interface
293
Field
Data entered
Wait time after successful ping 5
To make the BCM2 declare the inaccessibility of the monitored
PDU when that PDU becomes inaccessible for around 12
seconds (4 seconds * 3 pings), enter the following data.
Field
Data entered
Wait time after unsuccessful ping 4
Number of consecutive unsuccessful pings for
failure
3
To make the BCM2 stop pinging the target PDU for 60 seconds (1
minute) after the PDU inaccessibility is declared. After 60
seconds, the BCM2 will re-ping the target PDU, enter the
following data.
Field
Data entered
Wait time before resuming pinging after
failure
60
The "Number of consecutive failures before disabling feature (0 =
unlimited)" can be set to any value you want.
5. Click Create.
Step 2: Create an event rule to send SNMP notifications for the
target PDU
1. Choose Device Settings > Event Rules.
2. Click .
3. Select the Enabled checkbox to enable this new rule.
4. Configure the following.
Field/setting
Data specified
Rule name Send SNMP notifications for PDU
(192.168.84.95) inaccessibility
Event Choose Server Monitoring >
192.168.84.95 > Unreachable
Trigger condition Select the Unreachable radio button
This will make the BCM2 react only when the target PDU becomes
inaccessible.