Chapter 2: Connecting External Equipment (Optional)
72
a. Affix the adhesive part of the asset tag to one side of a blade
server through the tag's tape.
b. Plug the tag connector of the asset tag into a tag port on the
blade extension strip.
4. Repeat the above step until all blade servers in the chassis are
connected to the blade extension strip via asset tags.
5. Plug the tag connector of the blade extension strip into the closest
tag port of the regular or composite asset strip on the rack.
6. Repeat the above steps to connect additional blade extension strips.
Up to 128 asset tags on blade extension strips are supported per
FEATURE port.
Note: If you need to temporarily disconnect the blade extension strip
from the asset strip, wait at least 1 second before re-connecting it back,
or the BCM2 device may not detect it.