CHAPTER 8
70 Hawkeye Nozzle Control Operation Manual
Bypass nozzles if they go back. Remove the NCV and replace with a jumper plug. Take the
nozzle tip and reduce it to about half the original size.
Unplug the nozzle from the NCV and place the jumper plug on.
Turn on the secondary nozzle body.
Pressure inaccurate or unstable. Verify the correct pressure for the transducer is selected.
In Pressure Settings, adjust the Response rate to stabilize the
system.
Verify the pressure on VT matches separate external mechanical
gauge.
Individual nozzle will not communicate
with Raven Service Tool Action
Verify power to the nozzle.
Verify pin 5 “sw in” is three volts.
With DWM, measure resistance across pins 2 and 4. It should
measure 60-80k ohms.
Problem Action