TTDM-128 Installation Instructions
2
ResetTest
EnterEsc
Menu
TraceTek
TTDM
1
2
6
3
4
5
798 bk
bl
bm
bn
bo
bp
bq
brbsbtck
dk
clcmcnco
PL PL PL
cp
cq
cr
cs
ct
PL
1 LCD display
2 LEDs with icons
3 Test key
4 Silence key
5 Reset key
6 Menu keys
7 User Interface board
8 4–20 mA board (optional)
9 Sensor Interface board
bk Motherboard
bl Power supply board
bm Fuse (500 mA, 250 V, time delay)
bn Power cable terminal block
bo Voltage Selector Switch
bp Spare fuse
bq Ground/earth stud
br Gland plate
bs Fault relay cable plug and socket
bt Leak relay cable plug and socket
ck Service relay cable plug and socket
cl 4–20 mA port plug and socket
cm RS-232/485 host port plug and socket
cn Sensing cable plug and socket
co RS-485 TraceTek Network Plug
& Socket
cp Ribbon cable
cq Host port RS-232/485 selector
cr 9 pin RS-232 socket
cs Reset pins
ct Volume adjustment
dk LCD contrast adjustment
PL indicates power limited circuits
Note: To avoid damage to the unit, store the TTDM module in its
cardboard box until construction is complete.
Select the mounting position.
Choose a location indoors where the module will be protected from
the elements and temperature extremes.
Remove the module from its carton. Do not remove the protective film
from the membrane on the front of the unit.
Open the enclosure door using a flat-blade screwdriver or a coin.
Important: The TTDM is an electronic unit. During installation, take
the following precautions to avoid damage to its electronic components:
Handle with care, avoid mechanical damage.
Keep the electronics dry.
If handling circuit boards, hold them by their edges to avoid physical
contact with electronic components.
•Avoid exposure to static electricity.
•Avoid contamination with metal filings, liquids, or other foreign matter.
Installing the TTDM
WARNING: Ignition hazard. Do not mount the TTDM unit in a
hazardous location. Sensing cable connected to the TTDM may (subject
to approvals restrictions) be located in hazardous locations, but the
module itself must be in an ordinary area.
Note: The TraceTek sensing circuit is power limited, so the TraceTek
leader or jumper cable and the power supply cable must not run in
the same conduit.