40011/40027
26
COILS TABLE
COIL ADDRESS COIL NAME ACCESS
COMMENTS
1 Calibration Checksum Error 40505 (bit 0) Read/Write
2 Parameter Checksum Error 40505 (bit 1) Read/Write
3 40505 (bit 2) Read/Write
4 40503 Read/Write
1 = Disables writes to the non-volatile memory; Returns to 0(writes are enabled) at
power cycle.
CH A CH B
5 17 Shorted RTD Input Error 40504 Read Only
1 = Shorted RTD; Causes process value to be -32002, disables alarms, sets control
output(s) to sensor failure power preset level, causes flashing LEDs.
6 18 40504 Read Only
1 = Input Error; Causes process value to be 32002, disables alarms, sets control
output(s) to sensor failure power preset level, causes flashing LEDs.
7 19
Process Value (<-32000)
Under Range Input Error
Signal or Sensor Under
Range Input Error
40504
40504
Read Only
Read Only
1 = Under Range Error; Causes process value to be -32001, maintains control
output at present level, causes flashing LEDs.
8 20
Process Value (>32000)
Over Range Input Error
Signal or Sensor Over
Range Input Error
40504
40504
Read Only
Read Only
1 = Over Range Error; Causes process value to be 32001, maintains control output
at present level, causes flashing LEDs.
9 21 Control Output OP1 State 40014/40030 Read Only
0 = Off, 1 = On
10 22 Alarm 1 Output AL1 State 40015/40031 Read/Write
0 = Off, 1 = On; A write of 1 is only possible when alarm is set for Manual.
11 23 40016/40032 Read/Write
0 = Off, 1 = On; A write of 1 is only possible when alarm is set for Manual.
12 24 Control Mode 40041/40049 Read/Write
0 = Automatic Mode, 1 = Manual Mode
13 25 Disable Setpoint Ramping 40042/40050 Read/Write
0 = Enabled, 1 = Disabled
14 26 Setpoint Ramping In Process 40043/40051 Read Only
0 = No, 1 = Yes
15 27 Disable Integral Action 40044/40052 Read/Write
0 = Enabled, 1 = Disabled
33
31
30
29
16
32
28
Local/Remote Setpoint Select
Advance Profile Phase
SETPOINT CONTROLLER MODEL ONLY
Auto-Tune Start
40046
40070/40078
40505 (bit 5)
40505 (bit 4)
40011/40027
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
0 = Local Setpoint; 1 = Remote Setpoint
1 = Advance running Profile to next phase
1 = Checksum Error in A or B Setpoint Controller Operating Status memory, disables
control and alarm outputs, causes flashing LEDs, and aborts profile putting channel
in manual control at 0% power.
0 = Stop, 1 = Start
INPUT TYPE REGISTER (40101/40201) TABLE
ANALOG OUTPUT ASSIGNMENT REGISTER
(400301/40309) TABLE
SERIAL BAUD RATE REGISTER (40402) TABLE
ALARM 1 (40131/40231) AND ALARM 2
(40136/40236) ACTION REGISTER TABLE
MODE TYPE
0 Thermocouple - T
1 Thermocouple - E
2 Thermocouple - J
3 Thermocouple - K
4 Thermocouple - R
5 Thermocouple - S
6 Thermocouple - B
8
7
Thermocouple - C
Thermocouple - N
Process Current, Square Root Ext.
Process Current
17
16
15
Process Voltage14
Linear mV (1 = 10mV)13
Linear Ohms12
RTD nickel 67211
RTD platinum 39210
RTD platinum 3859
TYPEMODE
MODE ASSIGNMENT
0 Output Power A
1 Process Value A
2 Setpoint A
3 Ramping Setpoint A
4 Deviation A
5 Direct Entry Value 1
6 Output Power B
7 Process Value B
8 Setpoint B
9 Ramping Setpoint B
10 Deviation B
11 Direct Entry Value 2
MODE ACTION
0 Manual
1 Absolute HI (Balanced)
2 Absolute LO (Balanced)
3 Absolute HI (Unbalanced)
4 Absolute LO (Unbalanced)
5 Deviation HI
6 Deviation LO
7 Band Inside Acting
8 Band Outside Acting
9 Cooling (Alarm 2 only)
MODE BAUD
0 300
1 600
2 1200
3 2400
4 4800
5 9600
6 19200
7 38400
Integral and Offset/Manual
Power Checksum Error
MIRROR REGISTER
Alarm 2 Output AL2/OP2 State
1 = Under Range Error; Causes process value to be -32003, maintains control
output at present level until input causes Sensor FailurePower Preset Level, causes
flashing LEDs.
1 = Over Range Error; Causes process value to be 32003, maintains control output
at present level until input causes Sensor FailurePower Preset Level, causes
flashing LEDs.
Open Thermocouple, RTD, or
Extreme Process Input Over/
Under Range Input Error
Non-Volatile Memory Write
Disable
Setpoint Controller Segment
Memory Checksum Errror
Setpoint Controller Status
Memory Checksum Error
1 = Checksum Error in A or B Setpoint Controller Segment memory (40601-40760),
causes process value to be 32100 disables control and alarm outputs, causes
flashing LEDs.
1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs,
causes flashing LEDs. Writing a zero clears the error.
1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs,
causes flashing LEDs. Writing a zero clears the error.
1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs,
causes flashing LEDs. Writing a zero clears the error.
Process Voltage, Square Root Ext.