7
8
1110
9
ANALOG OUTPUT
0-10V, 0(4)-20mA
OUT -
OUT +
TBB
Controller,
Recorder
+
-
Output 1 = Terminals 8 & 9
Output 2 = Terminals 10 & 11
4
7
SETTING
OUTPUT COMMON
DEFAULT SERIAL
TBA
TBB
ANALOG DC OUTPUT CONNECTIONS
DEFAULT SERIAL SETTING CONNECTIONS
Note: Analog Outputs & RS485 are not internally isolated and must not
share the same common (i.e., earth ground).
If using software selectable serial
settings and the serial settings are
unknown or forgotten, they can be
temporarily reset to the defaults by
connecting the “Default Serial
Setting” terminal 7 to “Output
Common” terminal 4 with a jumper.
RS485 SERIAL CONNECTIONS
There are two modular connectors located on the front for paralleling
communications. The CBPRO007 programming cable converts the RS232 port
of a PC to RS485 and is terminated with an RJ11 connector. The bi-directional
capability of the CBPRO007 allows it to be used as a permanent interface cable
as well as a programming cable.
none
8
Parity:
Data Bits:
9600Baud Rate:
247Address:
RTUProtocol:
Defaults:
STEP 5 INSTALLING SFDLC (Software for DLC)
After downloading RLCPro for DLC Series (http://www.redlion.net/
SFDLC) open the ZIP archive and then run dlc207.exe to install the
software.
STEP 6 PROGRAMMING - Getting Started
Run RLCPro by double-clicking the icon, or use the start menu.
You will be prompted to
select the proper device,
Use the FILE pull-down menu
to select a NEW file.
and then the model.