The DIP switches for the various operating modes are located on the side of
the unit. For Reset to Zero modes, the UP/DN terminal is normally NOT
connected to common (count up). For Reset to Preset modes, the UP/DN
terminal is normally connected to common (count down). The unit will maintain
normal operating functions if the direction is reversed.
Note: During automatic reset, no counts will be missed if the count rate does not
exceed the maximum count rate specified. A manual reset, either from the
front panel reset (if enabled) or remote reset overrides any condition or state
of the counter and begins the cycle again.
Note: In modes four and twelve (Single preset) and in modes four, five, twelve,
and thirteen (Dual preset) the output may appear to be latched if the time
delay is longer than the time required to count from the reset condition to the
preset point.
MODE 0 LATCH OUTPUT AT PRESET, MANUAL RESET TO ZERO
The unit counts from zero, when the preset value is reached,
the output turns on and counts continue to accumulate. When
a manual reset is performed, the count resets to zero and the
output turns off.
MODE 1 TIMED OUTPUT AT PRESET, MANUAL RESET TO ZERO
The unit counts from zero, when the preset is reached the
output turns on for the amount of time programmed and
counts continue to accumulate. When a manual reset is
performed, the unit resets to zero and starts the cycle again.
MODE 2 & 3 -
*
MODE 4 TIMED OUTPUT AT PRESET, AUTOMATIC RESET TO ZERO AT PRESET
The unit counts from zero, when the preset is reached, the
output turns on for the amount of time programmed. At preset,
the unit automatically resets to zero and starts the counting
cycle over again.
MODE 5 -
*
MODE 6 TIMED OUTPUT AT PRESET, AUTOMATIC RESET TO ZERO AFTER THE
TIMED OUTPUT
The unit counts from zero, when the preset is reached the
output turns on for the amount of time programmed. At the
end of the timed output, the unit automatically resets to zero
and starts the cycle over again.
MODE 7 -
*
*
- These modes are not applicable to the single preset Lynx counter (they are
used only for the dual preset counter unit).
MODE 8 LATCH OUTPUT AT ZERO, MANUAL RESET TO PRESET ✝
The unit counts from preset, when zero is reached the output
turns on and counts continue to accumulate . When a manual
reset is performed, the unit resets to preset, the output turns off,
and the cycle starts again.
MODE 9 TIMED OUTPUT AT ZERO, MANUAL RESET TO PRESET ✝
The unit counts from preset, when zero is reached, the
output turns on for the amount of time programmed and counts
continue to accumulate. When a manual reset is performed, the
unit resets to preset and starts the cycle again.
MODE 10 & 11 -
*
MODE 12 TIMED OUTPUT AT ZERO, AUTOMATIC RESET TO PRESET AT ZERO ✝
The unit counts from preset, when zero is reached, the
output turns on for the amount of time programmed. At zero,
the unit automatically resets to preset and starts the counting
cycle again.
MODE 13 -
*
MODE 14 TIMED OUTPUT AT ZERO, AUTOMATIC RESET TO PRESET AFTER THE
TIMED OUTPUT
✝
The unit counts from preset, when zero is reached, the
output turns on for the amount of time programmed. At the end
of the timed output, the unit automatically resets to preset and
starts the cycle over.
MODE 15 -
*
✝ - When down count is desired, (such as reset to preset modes of operation)
the “UP/DN” terminal must be tied to the “COMM.” terminal.
MODES OF OPERATION, DIP SWITCH SET-UP
MODES OF OPERATION FOR SINGLE PRESET LYNX COUNTER
MODE 0 LATCH OUTPUTS AT PRESET, MANUAL RESET TO ZERO
The unit counts from zero, when preset 1 is reached,
output 1 turns on and counts continue to accumulate. When
preset 2 is reached, output 2 turns on and counts continue to
accumulate. When a manual reset is performed, the count resets to zero and
the outputs turn off.
MODE 1 TIMED OUTPUTS AT PRESET, MANUAL RESET TO ZERO
The unit counts from zero, when preset 1 is reached,
output 1 turns on. When preset 2 is reached, output 2 turns
on. Counts continue to accumulate after the preset levels
have been reached. The outputs turn off after their respective programmed
time values. When a manual reset is performed, the unit resets to zero and
starts the cycle again.
MODE 2 OUTPUT 1 TURN OFF AT PRESET 2, LATCH OUTPUT 2 AT PRESET 2,
MANUAL RESET TO ZERO
The unit counts from zero, when preset 1 is reached,
output 1 turns on. When preset 2 is reached, output 2 turns
on and output 1 turns off. Counts continue to accumulate
after the preset levels have been reached. Output 2 remains on until a manual
reset occurs. Manual reset turns off both outputs and the count resets to zero.
MODE 3 OUTPUT 1 TURN OFF AT PRESET 2, TIMED OUTPUT 2 AT PRESET 2,
MANUAL RESET TO ZERO
The unit counts from zero, when preset 1 is reached,
output 1 turns on. When preset 2 is reached, output 2 turns
on for the amount of time programmed and output 1 turns
off. Counts continue to accumulate after the preset levels have been reached.
When a manual reset is performed, the count resets to zero.
MODE 4 OUTPUT 1 TURN OFF AT PRESET 2, TIMED OUTPUT 2 AT PRESET 2,
AUTOMATIC RESET TO ZERO AT PRESET 2
The unit counts from zero, when preset 1 is reached,
output 1 turns on. When preset 2 is reached, output 2 turns
on for the amount of time programmed. At the beginning of
timed output 2, output 1 turns off and the unit automatically resets to zero.
MODE 5 TIMED OUTPUTS AT PRESETS, AUTOMATIC RESET TO ZERO AT PRESET 2
The unit counts from zero, when preset 1 is reached,
output 1 turns on, and when preset 2 is reached, output 2
turns on. The outputs turn off at the end of their respective
programmed time values. At preset 2, the count automatically resets to zero
and starts the cycle again.
MODE 6 OUTPUT 1 TURN OFF AT PRESET 2, TIMED OUTPUT 2 AT PRESET 2,
AUTOMATIC RESET TO ZERO AFTER TIMED OUTPUT 2
The unit counts from zero, when preset 1 is reached,
output 1 turns on. When preset 2 is reached, output 2 turns
on for the amount of time programmed and output 1 turns
off. At the end of timed output 2, the count automatically resets to zero and
starts the cycle again.
MODE 7 TIMED OUTPUTS AT PRESETS, AUTOMATIC RESET TO ZERO AFTER TIMED
OUTPUT 2
The unit counts from zero, when preset 1 is reached,
output 1 turns on, and when preset 2 is reached, output 2
turns on. The outputs turn off at the end of their respective
programmed time values. At the end of timed output 2, the unit automatically
resets to zero and starts the cycle again.
*
- Prescale EN./DIS. Switch.
MODES OF OPERATION FOR DUAL PRESET LYNX COUNTER