EasyManua.ls Logo

Rheem A18AZ Series - Installation; Tools and Refrigerant

Rheem A18AZ Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
4.0 INSTALLATION
Tools
4.1 Tools and Refrigerant
4.1.1 Tools Required for Installing
and Servicing R-410A Models
Manifold Sets:
– Up to 800 PSIG [5,516 kPa] High-Side
– Up to 250 PSIG [1,724 kPa] Low-Side
– 550 PSIG [3,792 kPa] Low-Side Retard
Manifold Hoses:
– Service Pressure Rating of 800 PSIG [5,516 kPa]
Recovery Cylinders:
– 400 PSIG [2,758 kPa] Pressure Rating
– Dept. of Transportation 4BA400 or BW400
Item Number Descripton
1 Ambient and Tube Thermometers
2 Crescent Wrench
3 Allen Wrench
4 Manifold Gauge Set
5 Brazing Rods
6 Recovery Cylinders
7 Nitrogen
8 Torch
9 Reclaimer
Figure 2: Required Tools for Unit Installation
CAUTION:
R-410A systems operate at higher pressures than
R-22 systems. Do not use R-22 service equipment or
components on R-410A equipment.
4.1.2 Specications of R-410A
Application: R-410A is not a drop-in replacement
for R-22. Equipment designs must accommodate its
higher pressures. It cannot be retrofitted into R-22 heat
pumps.
Physical Properties: R-410A has an atmospheric
boiling point of -62.9°F [-52.7°C] and its saturation
pressure at 77°F [25°C] is 224.5 psig [1,548 kPa].
Composition: R-410A is a near-azeotropic mixture of
50% by weight difluoromethane (HFC-32) and 50% by
weight pentafluoroethane (HFC-125).
Pressure: The pressure of R-410A is approximately
60% (1.6 times) greater than R-22. Recovery and
recycle equipment, pumps, hoses, and the like must
have design pressure ratings appropriate for R-410A.
Manifold sets need to range up to 800 psig [5,516
kPa] high-side and 250 psig [1,724 kPa] low-side with
a 550 psig [3,792 kPa] low-side retard. Hoses need to
have a service pressure rating of 800 psig [5,516 kPa].
Recovery cylinders need to have a 400 psig [2,758
kPa] service pressure rating, DOT 4BA400 or DOT
BW400.
Combustibility: At pressures above 1 atmosphere, a
mixture of R-410A and air can become combustible.
R-410A and air should never be mixed in tanks
or supply lines or be allowed to accumulate in
storage tanks. Leak checking should never be
done with a mixture of R-410A and air. Leak-
checking can be performed safely with nitrogen or a
mixture of R-410A and nitrogen.
4.1.3 Quick-Reference Guide for
R-410A
R-410A refrigerant operates at approximately 60%
higher pressure (1.6 times) than R-22. Ensure that
servicing equipment is designed to operate with
R- 410A .
R-410A refrigerant cylinders are light rose in color.
R-410A, as with other HFCs, is only compatible
with POE oils.
Vacuum pumps will not remove moisture from POE
oil used in R-410A systems.
R-410A systems are to be charged with liquid
refrigerants. Prior to March 1999, R-410A
refrigerant cylinders had a dip tube. These
cylinders should be kept upright for equipment
charging. Post-March 1999 cylinders do not have
a dip tube and should be inverted to ensure liquid
charging of the equipment.
Do not install a suction line filter drier in the liquid
line.
A factory-approved bi-flow liquid line filter drier
is shipped with every unit and must be installed
in the liquid line at the time of installation. Only
manufacturer-approved liquid line filter driers
should be used. Filter driers must have a working
pressure rating of at least 600 psig [4,137 kPa].
The filter drier will only have adequate moisture-
holding capacity if the system is properly
evacuated.
Desiccant (drying agent) must be compatible for
POE oils and R-410A refrigerant.
1
2
3
4
5
6
7
8
9

Table of Contents

Related product manuals