Commercial Air to Water Heat Pump Water Heater
24
SIDES 60K BTU MODELS 135K BTU MODELS
Evap Coil Side 20 in (500 mm) 40 in (1000 mm)
Back (vertical discharge models) Nil Nil
Back (horizontal discharge models) 47 in (1200 mm) 78 in (2000 mm)
Display Side 34 in (850 mm) 34 in (850 mm)
Water Connections Side 20 in (500 mm) 24 in (600 mm)
Top (vertical discharge models) 47 in (1200 mm) 79 in (2000 mm)
Top (horizontal discharge option) Clearance above unit required for service personnel to stand.
CLEARANCES- AIR TO WATER HEAT PUMP MODELS
INSTALLATION