Line voltage must be present at the ICC for the compressor and the outdoor fan
to operate
The ICC displays a “0” for standby mode. Standby mode indicates line voltage
and 24VAC are present at the ICC and there is not a command for unit operation
from the Comfort Control
2
thermostat.
Zero (0) displayed
The unit is in standby
Command for Compressor Operation (Y1 LED)
If a command for compressor operation is received by the ICC (first stage/second
stage cooling or first stage/second stage heating), the red Y1 LED will illuminate.
The ICC has an on/off fan delay of one (1) second for each stage of heating or
cooling.
The ICC ignores the low pressure control for the first 90 seconds of compressor
operation.
The dual 7-segment LED displays five (5) operational status codes.
1) First Stage Cooling Operation When the ICC receives a command for first
stage cooling operation, a lower case “c” is displayed on the dual 7-segment LEDs.
Lower case “c” indicates first stage cooling operation
2) Second Stage Cooling Operation When the ICC receives a command for
second stage cooling operation, an upper case “C” is displayed on the dual 7-
segment LEDs.
Upper case “C” indicates second stage cooling operation
3-minute Anti-short Cycle Timer
The ICC has a built in 3-minute time delay between compressor operations to
protect the compressor against short cycling. The dual 7-segment LEDs will flash
“c” or “C” while the short cycle timer is active and a command for unit operation is
received.
19
FIGURE 5
T
YPICAL COMFORT CONTROL
2
S
YSTEM™ WIRING DIAGRAM
Indoor Unit
1
2
C
R
WIRING INFORMATION
Line Voltage
–Field Installed - - - - - -
Factory Standard
1
2
R
C
1
2
R
C
Communicating Thermostat
Outdoor Unit
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING