30 Second Minimum Run Timer
The ICC has a built in 30 second minimum unit run time. If a call for compressor
operation is received by the ICC and the call is removed, the compressor will con-
tinue to operate for 30 seconds. The dual 7-segment LEDs will flash “c” or “C”
while the minimum run timer is active.
1 Second Compressor/Fan Delay
The ICC starts/stops the outdoor fan one (1) second after the start/stop of the
compressor upon a call for compressor operation to minimize current inrush
and/or voltage drop.
11.10 Active Compressor Protection Mode
The ICC actively protects the compressor from harmful operation during a fault
condition.
When the ICC detects a condition that could damage the compressor, the ICC will
enter active protection mode and lockout compressor operation
The condition causing active protection must be resolved then the ICC can be
reset to restart the system.
There are five (5) active protection modes:
1) Low Pressure Control Lockout
The ICC will display a flashing “L” followed by a flashing 21 when a low pressure
control lockout occurs.
The ICC addresses low pressure control faults differently depending on the mode
of unit operation (cooling or heating mode).
Active Protection Code L21 Open low pressure control
Cooling Mode
If the LPC opens three (3) times during the same call for cooling operation, the
ICC will lockout the compressor to keep it from continuing to operate and flash a
L” on the dual 7-segment LEDs followed by a “21”.
IMPORTANT: This mode of active protection must be manually reset.
2) High Pressure Control Lockout
If the HPC opens three (3) times during the same call for unit operation, the ICC
will lockout the compressor to keep it from continuing to operate and flash a L” on
the dual 7-segment LEDs followed by a “29”.
Active Protection Code L29 Open high pressure control
IMPORTANT: This mode of active protection must be manually reset.