LED Error Code Listing
Active errors detected are indicated by LED lights on the PIM™.
Table X: PIM™ LED Error Codes
LED Code Error Mode Recommended Troubleshooting
Off Normal Operation
Red LED
steady ON,
Green Power
LED OFF
ID Card Fault
Check that the proper ID card is securely connected. Perform a
power and system restart.
Steady ON Internal Control Failure Perform a power and system reset. If fault remains, replace PIM™.
1 flash N/A N/A
2 flashes False Flame Error Check for proper gas valve closure. Clean burner and electrodes.
3 flashes Ignition Lockout Fault Check the gas supply. See table for more information.
4 flashes N/A N/A
5 flashes Low Voltage Fault
Check the 24 VAC input voltage. The voltage must be above 18.0
VAC.
6 flashes N/A N/A
7 flashes Hi-Limit Fault Check for proper water flow. Check hi-limit and outlet sensor.
8 flashes Sensor Fault See VERSA for fault identification. Check sensor wiring.
9 flashes N/A N/A
10 flashes N/A N/A
11 flashes N/A N/A
12 flashes N/A N/A
13 flashes
Hi-Temperature Delta
Fault
Check pump operation. Confirm proper water flow across heat
exchanger.
14 flashes
Ft-Bus
Communications Fault
Verify VERSA is connected and operating. Check the cable between
the VERSA and PIM™.
15 flashes Safety circuit open
Confirm all safeties are functioning normally. Check continuity at J8,
pins 5 and 6 at the PIM™.