NOTICE
Improper installation, or installation not made in accordance with the
Underwriters Laboratory (UL) certification or these instructions, can result
in unsatisfactory operation and/or dangerous conditions and are not cov-
ered by the unit warranty.
!
NOTICE
In compliance with recognized codes, it is recommended that an auxiliary
drain pan be installed under all evaporator coils or units containing evapo-
rator coils that are located in any area of a structure where damage to the
building or building contents may occur as a result of an overflow of the
coil drain pan or a stoppage in the primary condensate drain piping. See
accessories section of these instructions for auxiliary horizontal overflow
pan information (model RXBM).
!
CAUTION
When used on cooling applications, excessive sweating may occur when unit
is installed in an unconditioned space. This can result in property damage.
Some building codes require extra cabinet insulation and gasketing when
unit is installed in attic applications.
If installed in an unconditioned space, apply caulking around the power
wires, control wires, refrigerant tubing and condensate line where they enter
the cabinet. Seal the power wires on the inside where they exit conduit
opening. Caulking is required to prevent air leakage into and condensate
from forming inside the unit, control box, and on electrical controls.
Install the unit in such a way as to allow free access to the coil/filter com-
partment and blower/control compartment.
Install the unit in a level position to ensure proper condensate drainage.
Make sure unit is level in both directions within 1/8”.
Install the unit in accordance with any local code which may apply and the
national codes. Latest editions are available from: “National Fire Protection
Association, Inc., Batterysmarch Park, Quincy, MA 02269. These publications
are:
ANSI/NFPA No. 70-(Latest Edition) National Electrical Code.
NFPA90A Installation of Air Conditioning and Ventilating Systems.
NFPA90B Installation of warm air heating and air conditioning systems.
The equipment has been evaluated in accordance with the Code of Federal
Regulations, Chapter XX, Part 3280.
!
CAUTION
HORIZONTAL UNITS MUST BE CONFIGURED FOR RIGHT HAND AIR SUPPLY
OR LEFT HAND AIR SUPPLY. HORIZONTAL DRAIN PAN MUST BE LOCATED
UNDER INDOOR COIL. FAILURE TO USE THE DRAIN PAN CAN RESULT IN
PROPERTY DAMAGE.