28
5.3 115/208/480V AIRFLOW PERFORMANCE DATA – (-)HSL (PSC MOTOR) - continued
NOTE:
All 208/240V PSC motors have voltage taps for 208 and 240 volts.
All 208/240V PSC motors are shipped on high speed and 240 volts.
All 115V PSC motors are shipped on high speed.
If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below:
- Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
- Replace the cap on the black motor wire.
Voltage change (208/240V motors):
- Move the orange lead to transformer to 208V tap from 240V tap. Replace the wire cap on 240V tap.
- Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
- Replace the cap on the purple motor wire.
All 480V PSC motors are shipped on high speed.
If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below for 3-ton through
4-ton air handlers.
- Unplug the black motor wire off the relay and remove the cap from the red motor wire.
- Plug the red motor wire to the relay and connect the black motor wire with the yellow motor wire.
For 5-ton air handler, unplug the black motor wire off the relay and plug in the red motor wire, then cap the black motor wire.
There is no yellow motor wire on 5-ton air handler.
WARNING: Do not connect red motor wire with yellow motor wire in any circumstance on 480V PSC motors. Connecting red motor wire with
yellow motor wire will result in permanent motor damage.
The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each
model.
The following formula can be used to calculate the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) X (N kw/maximum heater kw)
Model
Number
Motor
Speed
From
Factory
Manufacturer
Recommended
Air Flow Range
(Min / Max) CFM
Blower Size/
Motor H.P.
[W]
# of Speeds
Motor
Speed
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
1488 [702] 1419 [670] 1466 [692] 1430 [675] 1395 [658] ——
812 861 912 943 973 ——
554 545 526 508 491 ——
——1824 [861] 1767 [834] 1653 [780]
—— 1102 1112 1121
—— 871 830 770
1418 [669] 1349 [637] 1396 [659] 1360 [642] 1325 [625] ——
862 899 935 965 995 ——
534 525 506 588 471 ——
——1724 [814] 1667 [787] 1553 [733]
——1116 1119 1130
—— 810 780 730
1866 [881] 1833 [865] 1806 [852] 1772 [836] 1710 [807] ——
764 803 824 856 886 ——
514 756 733 715 701 ——
—— 1967 [928] 1916 [904] 1863 [879]
—— 948 959 991
——850 827 816
1796 [848] 1763 [832] 1736 [819] 1702 [803] 1640 [774] ——
828 860 878 890 1001 ——
735 718 705 695 678 ——
——1867 [881] 1816 [857] 1763 [832]
—— 989 1005 1020
—— 818 795 780
-4821/-4824
No heater
High
1395/1824 CFM
[658/861 L/s]
10x10
3/4HP[559]
2 Speed
Low
High
-4821/-4824
with
25kw heater
High
1225/1500 CFM
[625/814 L/s]
10x10
3/4HP[559]
2 Speed
Low
High
-6024
No heater
High
1710/1967 CFM
[807/928 L/s]
11x11
3/4HP[559]
2 Speed
Low
High
-6024
with
30kw heater
High
1640/1796 CFM
[773/847 L/s]
11x11
3/4HP[559]
2 Speed
Low
High
PSC CFM[L/s] Air Delivery/RPM/Watts-240 Volts
External Static Pressure-Inches W.C.
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]