5.4 115/208/240/480V AIRFLOW PERFORMANCE DATA – (-)HLL (X-13 MOTOR) - continued
Model
Number
Motor
Speed
From
Factory
Tonnage
Application
Manufacturer
Recommended
Air Flow Range
(Min / Max) CFM
Blower Size/
Motor H.P.
# of Speeds
Motor
Speed
X-13
CFM[L/s] Air Delivery/RPM/Watts-115/208/240 Volts
External Static Pressure-Inches W.C.
0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17]
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
1748 [825] 1669 [788] 1639 [773] 1599 [755] 1545 [729] ——
660 698 734 762 795 ——
297 311 326 340 353 ——
—— — —1732 [817] 1683 [794] 1630 [769]
— ———840 872 899
— ———448 467 480
1708 [806] 1629 [769] 1599 [755] 1559 [736] 1505 [710] ——
680 736 760 790 820 ——
305 330 341 350 361 ——
—— — —1692 [798] 1643 [775] 1590 [750]
—— — —865 890 1014
— ———460 470 481
1902 [898] 1862 [879] 1809 [854] 1781 [840] 1739 [821] ——
712 749 787 815 856 ——
389 409 419 432 459 ——
— ———1905 [899] 1866 [881] 1832 [865]
—— — —894 924 950
—— — —565 570 592
1862 [879] 1822 [860] 1769 [835] 1741 [822] 1699 [802] ——
750 790 810 850 880 ——
410 420 430 455 479 ——
—— — —1865 [880] 1826 [862] 1792 [846]
— ———920 945 970
—— — —565 587 610
1705 [805] 1661 [784] 1632 [770] 1572 [742] 1517 [716] ——
663 701 741 782 819 ——
292 309 321 343 357 ——
—— — —1697 [801] 1646 [777] 1601 [756]
—— — —857 895 920
—— — —447 466 473
1669 [788] 1625 [767] 1596 [753] 1537 [725] 1482 [700] ——
698 739 763 816 842 ——
308 317 329 361 373 ——
—— — —1661 [784] 1611 [760] 1566 [739]
—— — —882 915 939
—— — —447 480 487
4824
No heater
3
11x11
3/4 [559]
5 Speed
2
3
4824
with
25kw heater
3
11x11
3/4 [559]
5 Speed
2
3
5
1545/1732 CFM
[729/817 L/s]
11x11
3/4 [559]
5 Speed
4
5
5
5
5
1505/1692 CFM
[710/798 L/s]
11x11
3/4 [559]
5 Speed
11x11
3/4 [559]
5 Speed
11x11
3/4 [559]
5 Speed
4
5
2
3
2
3
-6024 No Heater
-6024 with 30kW
Heater
6024
No heater
6024
with
30kw heater
1739/1905 CFM
[821/899 L/s]
1699/1865 CFM
[802/880 L/s]
1517/1697 CFM
[716/801 L/s]
1482/1661 CFM
[700/784 L/s]
4.0
4.0
5.0
5.0
4 & 5
4 & 5
NOTE:
X-13 motor speed changes
All X-13 motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage. Speed tab 4 (low stat-
ic) and Speed tab 5 (high static) are for higher tonnage.
X-13 air handlers are always shipped from factory at speed tab 5, except for -4824, which is set at speed tab 3.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5” WC. The high static Speed tab 3 (lower tonnage) and 5 (higher
tonnage) are used for external static exceeding 0.5” WC. Move the blue wire to the appropriate speed tab as required by the application needs.
• The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) X (N kw/maximum heater kw)