BLOWER PERFORMANCE DATA*—RHWB- MODELS
MODEL
BLOWER
SIZE
[mm]
MOTOR
H.P.
[W]
BLOWER
SPEED
CFM [L/s] AIR DELIVERY
EXTERNAL STATIC PRESSURE INCHES WATER COLUMN [kPa]
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
RHWB-
04WMP36A
11 x 7
[279 x 178]
1/2
[373]
LOW
MED-LO
MED-HI
HIGH
794 [375]
1036 [489]
1202 [567]
1356 [640]
775 [366]
1024 [483]
1176 [555]
1336 [631]
749 [353]
1002 [473]
1160 [547]
1301 [614]
719 [339]
977 [461]
1100 [519]
1266 [597]
686 [324]
922 [435]
1073 [506]
1235 [583]
655 [309]
896 [423]
1047 [494]
1202 [567]
621 [293]
865 [408]
1008 [476]
1156 [546]
RHWB-
06WMP48A
11 x 7
[279 x 178]
1/2
[373]
LOW
MED-LO
MED-HI
HIGH
921 [435]
1189 [561]
1335 [630]
1841 [869]
915 [432]
1180 [557]
1312 [619]
1795 [847]
886 [418]
1179 [556]
1306 [616]
1747 [824]
876 [413]
1137 [537]
1307 [617]
1681 [793]
855 [404]
1131 [534]
1277 [603]
1622 [765]
841 [397]
1102 [520]
1246 [588]
1560 [736]
817 [386]
1072 [506]
1210 [571]
1500 [708]
RHWB-
08WRP60A
11 x 10
[279 x 254]
3/4
[559]
LOW
MED-LO
MED-HI
HIGH
1319 [623]
1484 [700]
1687 [796]
1971 [930]
1307 [617]
1480 [698]
1676 [791]
1974 [932]
1300 [614]
1471 [694]
1671 [789]
1948 [919]
1240 [585]
1463 [690]
1611 [760]
1929 [910]
1236 [583]
1418 [669]
1586 [749]
1871 [883]
1210 [571]
1385 [654]
1553 [733]
1806 [852]
1177 [555]
1359 [641]
1513 [714]
1751 [826]
RHWB-
10WRP60A
11 x 10
[279 x 254]
3/4
[559]
LOW
MED-LO
MED-HI
HIGH
1299 [613]
1515 [715]
1684 [795]
1954 [922]
1294 [611]
1519 [717]
1695 [800]
1971 [930]
1308 [617]
1499 [707]
1692 [799]
1974 [932]
1279 [604]
1487 [702]
1663 [785]
1982 [935]
1257 [593]
1415 [668]
1620 [765]
1973 [931]
1231 [581]
1418 [669]
1586 [749]
1944 [917]
1205 [569]
1394 [658]
1569 [740]
1917 [905]
0.8 [.19]
590 [278]
826 [390]
969 [457]
1093 [516]
780 [368]
1030 [486]
1161 [548]
1420 [670]
1149 [542]
1314 [620]
1453 [686]
1699 [802]
1165 [550]
1348 [636]
1514 [715]
1818 [858]
0.9 [.22]
534 [252]
761 [359]
926 [437]
1030 [486]
734 [346]
985 [465]
1090 [514]
1358 [641]
1100 [519]
1246 [588]
1389 [656]
1610 [760]
1122 [530]
1296 [612]
1451 [685]
1775 [838]
1.0 [.24]
473 [223]
689 [325]
890 [420]
959 [453]
690 [326]
915 [432]
1019 [481]
1288 [608]
1032 [487]
1166 [550]
1284 [606]
1511 [713]
1053 [497]
1221 [576]
1365 [644]
1700 [802]
*Blower performance measured without filter and cooling coil in place.
[ ] Designates Metric Conversions
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
period stated, in accordance with the terms of the limited
warranty.
*For Complete Details of the Limited Warranty, Including Applicable
Terms and Conditions, See Your Local Installer or Contact the
Manufacturer for a Copy.
Conditional Parts* (Registration Required).......Ten (10) Years
Hydronic Air Handler Warranty Terms
Labor* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . One(1)Year
AirHandlerHeatExchanger/Coil* . . . . . . . . . Five(5)Years
AnyOtherPart* . . . . . . . . . . . . . . . . . . . . . . . Five(5)Years