- 158 -
MULTI TYPE
2, 3, 4 ROOMS TYPE
5) Static pressure
Select the appropriate static pressure according to the installation conditions.
NOTE: Range of static pressure is different by model.
6)
Room temperature control for indoor unit sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
*When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No
correction 0.0 °F (0.0 °C)" (01).
In case of Slim duct type and Floor/Ceiling type models:
In floor console installations, select "01".
Function number Setting value Setting description Factory setting
26
00 0 in.WG (0 Pa)
01 0.04 in.WG (10 Pa)
02 0.08 in.WG (20 Pa)
03 0.12 in.WG (30 Pa)
04 0.16 in.WG (40 Pa)
05 0.20 in.WG (50 Pa)
06 0.24 in.WG (60 Pa)
07 0.28 in.WG (70 Pa)
08 0.32 in.WG (80 Pa)
09 0.36 in.WG (90 Pa)
31 0.10 in.WG (25 Pa) (Standard) Ƈ
Model name Range of static pressure
RIDH7AVFJ
0 to 0.36 in.WG (0 to 90 Pa)
RIDH9AVFJ
RIDH12AVFJ
RIDH18AVFJ
RIDH24AVFJ
0 to 0.20 in.WG (0 to 50 Pa)
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting* Ƈ
01 No correction 0.0 °F (0.0 °C)
02 -1 °F (-0.5 °C)
More cooling
Less heating
03 -2 °F (-1.0 °C)
04 -3 °F (-1.5 °C)
05 -4 °F (-2.0 °C)
06 -5 °F (-2.5 °C)
07 -6 °F (-3.0 °C)
08 -7 °F (-3.5 °C)
09 -8 °F (-4.0 °C)
10 +1 °F (+0.5 °C)
Less cooling
More heating
11 +2 °F (+1.0 °C)
12 +3 °F (+1.5 °C)
13 +4 °F (+2.0 °C)
14 +5 °F (+2.5 °C)
15 +6 °F (+3.0 °C)
16 +7 °F (+3.5 °C)
17 +8 °F (+4.0 °C)