¢ Indoor unit: 24,000 Btu
COOLING
Pipe length
m 5 7.5 10 15 20 25
m ft 16 25 33 49 66 82
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 49 0.978 0.969 0.953
10 33 0.986 0.986 0.977 0.961
7.5 25 0.988 0.990 0.990 0.981 0.965
5 16 0.989 0.992 0.994 0.994 0.984 0.968
0 0 0.997 1.000 1.002 1.002 0.992 0.976
Indoor unit is lower than
outdoor unit *2
-5 -16 0.997 1.000 1.002 1.002 0.992 0.976
-7.5 -25 1.000 1.002 1.002 0.992 0.976
-10 -33 1.002 1.002 0.992 0.976
-15 -49 1.002 0.992 0.976
HEATING
Pipe length
m 5 7.5 10 15 20 25
m ft 16 25 33 49 66 82
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 49 0.964 0.939 0.913
10 33 0.988 0.964 0.939 0.913
7.5 25 1.000 0.988 0.964 0.939 0.913
5 16 1.008 1.000 0.988 0.964 0.939 0.913
0 0 1.008 1.000 0.988 0.964 0.939 0.913
Indoor unit is lower than
outdoor unit *2
-5 -16 1.003 0.995 0.983 0.959 0.934 0.909
-7.5 -25 0.993 0.981 0.957 0.932 0.907
-10 -33 0.978 0.954 0.929 0.904
-15 -49 0.949 0.925 0.899
DESIGN & TECHNICAL MANUAL
- 118 -
OUTDOOR UNIT
ROMH45AFXZJ