Air
Accessories
RKNL-B Series
58
ENGINEERING DATA
➀
CONCENTRIC DIFFUSER—STEP DOWN
18" x 28" [457.2 x 711.2 mm]
RXRN-AA61 (8.5 & 10 Ton [29.9 kW & 35.2] Models)
For Use With Downflow Transition (RXMC-CE05)
and 18" x 28" [457.2 x 711.2 mm]
Supply and Return Ducts
■
All aluminum diffuser with aluminum
return air eggcrate.
■
Built-in anti-sweat gasket.
■
Molded fiberglass supports.
■
Built-in hanging supports.
■
Diffuser box constructed of sheetmetal
insulated with 1" [25.4 mm] 1.5 lbs.
[.7 kg] duct liner.
■
Double deflection diffuser with the
blades secured by spring steel.
Model No.
Flow Rate
CFM [L/s]
Static Pressure
in w.c. [kPa]
Throw ➁➂
Feet [m]
Neck Velocity
fpm [m/s]
Noise Level ➃
(dbA)
RXRN-AA61
3600 [1699] 0.17 [0.042] 25-33 [7.6-10.1] 851 [4.3] 30
3800 [1793] 0.18 [0.045] 27-35 [8.2-10.7] 898 [4.6] 30
4000 [1888] 0.21 [0.052] 29-37 [8.8-11.3] 946 [4.8] 30
4200 [1982] 0.24 [0.060] 32-40 [9.8-12.2] 993 [5.0] 30
4400 [2076] 0.27 [0.067] 34-42 [10.4-12.8] 1040 [5.3] 30
Illustration
ADS-7951-08A
Illustration
ADS-7951-08B
Illustration
ADS-7951-08C
NOTES: ➀ All data is based on the air diffusion council guidelines.
➁ Throw data is based on 75 FPM Terminal Velocities using isothermal air.
➂ Throw is based on diffuser blades being directed in a straight pattern.
➃ Actual noise levels may vary due to duct design and do not include transmitted unit noise.
Adequate duct attenuation must be provided to reduce sound output from the unit.
[ ] Designates Metric Conversions