ENGINEERING DATA
CONCENTRIC DIFFUSER—STEP DOWN
18" x 28" [457.2 x 711.2 mm]
RXRN-AA61 (8.5 & 10 Ton [29.9 kW & 35.2] Models)
For Use With Downflow Transition (RXMC-CE05)
and 18" x 28" [457.2 x 711.2 mm]
Supply and Return Ducts
All aluminum diffuser with aluminum
return air eggcrate.
Built-in anti-sweat gasket.
Molded fiberglass supports.
Built-in hanging supports.
Diffuser box constructed of sheetmetal
insulated with 1" [25.4 mm] 1.5 lbs.
[.7 kg] duct liner.
Double deflection diffuser with the
blades secured by spring steel.
Model No.
Flow Rate
CFM [L/s]
Static Pressure
in w.c. [kPa]
Throw ➁➂
Feet [m]
Neck Velocity
fpm [m/s]
Noise Level
(dbA)
RXRN-AA61
3600 [1699] 0.17 [0.042] 25-33 [7.6-10.1] 851 [4.3] 30
3800 [1793] 0.18 [0.045] 27-35 [8.2-10.7] 898 [4.6] 30
4000 [1888] 0.21 [0.052] 29-37 [8.8-11.3] 946 [4.8] 30
4200 [1982] 0.24 [0.060] 32-40 [9.8-12.2] 993 [5.0] 30
4400 [2076] 0.27 [0.067] 34-42 [10.4-12.8] 1040 [5.3] 30
Illustration
ADS-7951-08A
Illustration
ADS-7951-08B
Illustration
ADS-7951-08C
NOTES: All data is based on the air diffusion council guidelines.
Throw data is based on 75 FPM Terminal Velocities using isothermal air.
Throw is based on diffuser blades being directed in a straight pattern.
Actual noise levels may vary due to duct design and do not include transmitted unit noise.
Adequate duct attenuation must be provided to reduce sound output from the unit.
[ ] Designates Metric Conversions