Rheem ROSH12AFWJ - Capacity Compensation Rate for Pipe Length and Height Difference

Rheem ROSH12AFWJ
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- (02 - 08) -
OUTDOOR UNIT
ROSH09-12AFWJ
OUTDOOR UNIT
ROSH09-12AFWJ
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
MODEL : ROSH09AFWJ
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
COOLING
Pipe length
5m 7.5m 10m 15m 20m
16ft. 25ft. 33ft. 49ft. 66ft.
Height
difference H
Ú
1
Indoor unit is higher
than outdoor unit.
15m 49ft. - - - 0.872 0.910
10m 33ft. - - 0.961 0.886 0.925
7.5m 25ft. - 0.979 0.965 0.890 0.929
5m 16ft. 0.992 0.983 0.969 0.893 0.933
0m 0ft. 1.000 0.991 0.976 0.901 0.940
Ú
2
Indoor unit is lower
than outdoor unit
-5m -16ft. 1.000 0.991 0.976 0.901 0.940
-7.5m -25ft. - 0.991 0.976 0.901 0.940
-10m -33ft. - - 0.976 0.901 0.940
-15m -49ft. - - - 0.901 0.940
HEATING
Pipe length
5m 7.5m 10m 15m 20m
16ft. 25ft. 33ft. 49ft. 66ft.
Height
difference H
Ú
1
Indoor unit is higher
than outdoor unit.
15m 49ft. - - - 0.832 0.822
10m 33ft. - - 0.917 0.832 0.822
7.5m 25ft. - 0.961 0.917 0.832 0.822
5m 16ft. 1.000 0.961 0.917 0.832 0.822
0m 0ft. 1.000 0.961 0.917 0.832 0.822
Ú
2
Indoor unit is lower
than outdoor unit
-5m -16ft. 0.995 0.956 0.912 0.828 0.818
-7.5m -25ft. - 0.954 0.910 0.826 0.816
-10m -33ft. - - 0.908 0.824 0.814
-15m -49ft. - - - 0.815 0.805
H H