EasyManua.ls Logo

Rheem RTGH-90XLP-2 - Leak and Pressure Testing

Rheem RTGH-90XLP-2
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
INSTALLATION INSTRUCTIONS
Leak Testing
WARNING:
Never use an open flame to test for gas leaks, because
death, personal injury, and/or property damage can result.
The water heater and its gas connections MUST be leak-
tested at normal operating pressures before the unit is
placed in operation. These tests should also include all
factory connections.
Turn on the gas shut-off valve(s) to the water heater.
Use a soapy water solution to test for leaks at all
the connections and fittings. If bubbles are seen,it
indicates a gas leak that must be corrected.
Contact a qualified service technician.
Pressure Testing the Gas Supply System
WARNING:
If inlet gas pressure is out of allowable range [4.0” w.c.
(1.0kPa) – 10.5” w.c. (2.6kPa)] for Natural Gas, or [8.0”
w.c. (2.0kPa) – 13.0” w.c. (3.2kPa)] for LP gas, a gas
pressure regulator must be installed to maintain the
allowable inlet gas pressure.
The water heater and its manual gas shut-off valve
must be disconnected from the gas supply piping
system during any pressure testing of the system at
test pressures in excess of 1/2 psi (3.5 kPa).
The water heater must be isolated from the gas supply
piping system by closing the manual gas shut-off valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psi
(3.5 kPa).
Gas Supply

Related product manuals