Chapter6 Parameter Description of Pump
123
6
6-10 Flow Sensor
Func.
Name
Description
F_166
Flow Sensor
K Value
A default flow sensor K value, based on the flow sensor
specification.
F_167
Flow Sensor
Rate
Set up the rate of flow sensor.
Range: 0.00~2.00 (default: 1.00)
F_168
Flow Sensor
Display Unit
0 : LPS(l/sec) (default value)
1: CMH(m3/hr)
1. Flow sensor specification: Pulse input type.
2. Flow sensor formula:
Flow rate(I/sec)= Input pulses(pulse/sec)* Flow sensor K value( I/ pulse)* Flow sensor rate
3. Flow sensor input signal can connect multi-input terminal(X1~X4), F_52~F_055 set 21.