CONTROL BOX (see Fig. 10)
To remove the control-box from the burner, loosen screw (A) and
pull to the arrow direction, after removing all components, the
7 pin plug and earth wire.
In case of disassembly of the control box, retighten the
screw (A) with a torque wrench setting of 1 – 1.2 Nm.
S7072
Fig. 10
A
D1913
NOTES:
– Wires of min. 1 mm
2
section.
(Unless requested otherwise by local standards
and legislation).
– The electrical wiring carried out by the installer
must be in compliance with the rules in force in
the Country.
WARNING
DO NOT EXCHANGE NEUTRAL WITH PHASE
7 pin plug
7 pole socket
Black
White
Capacitor
Main switch
T6A
Motor
Blue
Oil valve
Hour counter
(230V - 0.
1A
max.)
Limit thermostat
Remote lock-out signal
(230V - 0.5A max.)
Ignition
electrodes
Brown
Burner-earth
552SE
CONTROL BOX
Sensor llama
PE L N
Blue
TESTING
Check the shut-down of the burner by opening
the thermostats and the lock-out by darkening
the sensor llama.
Safety thermostat
~50/60Hz 220/230V
CARRIED-OUT
IN THE FACTORY
TO BE DONE
BY THE INSTALLER