OPERATION PARAMETER #01
ADDRESS 6/9
OPERATION PARAMETER #01
ADDRESS 7/9
OPERATION PARAMETER #01
ADDRESS 8/9
OPERATION PARAMETER #01
ADDRESS 9/9
ODU MODEL 6kW
COMP. CURRENT 12A
COMP. FREQUENCY 24Hz
COMP. RUN TIME 54 MIN
COMP. TOTAL RUN TIME 1000Hrs
EXPANSION VALVE 200P
FAN SPEED 600R/MIN
IDU TARGET FREQUENCY 46Hz
FREQUENCY LIMITED TYPE 5
SUPPLY VOLTAGE 230V
DC GENERATRIX VOLTAGE 420V
DC GENERATRIX CURRENT 18A
TW_O PLATE W-OUTLET TEMP. 35°C
TW_I PLATE W-INLET TEMP. 30°C
T2 PLATE F-OUT TEMP. 35°C
T2B PLATE F-IN TEMP. 35°C
Th COMP. SUCTION TEMP. 5°C
Tp COMP. DISCHARGE TEMP. 75°C
T3 OUTDOOR EXCHARGE TEMP. 5°C
T4 OUTDOOR AIR TEMP. 5°C
TF MODULE TEMP. 55°C
P1 COMP. PRESSURE 2300kPa
ODU SOFTWARE 01-09-2018V01
HMI SOFTWARE 01-09-2018V01
i
INFORMATION
Thepowerconsumptionparameterisoptio-
nal. If some parameter is not be activated in
thesystem,theparameterwillshow"--".The
heat pump capacity is for reference only,
not used to judge the ability of the unit. The
accuracyofsensoris±1°C.Theowrates
parameters are calculated according to the
pump running parameters, the deviation is
di󰀨erentatdi󰀨erentowrates,themaximum
ofdeviationis15%.Theowparametersare
calculated according to the electrical para-
meters of the pump operation. The operating
voltageisdi󰀨erentandthedeviationisdi󰀨e-
rent.Thedisplayvalueis0whenthevoltage
is less than 198V.
7.9 FOR SERVICEMAN
7.9.1 About FOR SERVICEMAN
FOR SERVICEMAN is used for installer and
service engineer.
Setting the function of equipment.
Setting the parameters.
7.9.2 How To Go To FOR SERVICEMAN
Go to
> FOR SERVICEMAN. Press .
FOR SERVICEMAN
Please input password:
ENTER ADJUST
2 43
The FOR SERVICEMAN is used for
installer or service engineer. It is NOT
intended the home owner alters setting
withthismenu.
Itisforthisreasonpasswordprotectionis
required to prevent unauthorised access
to the service settings.
Thepasswordis234.
7.9.3 How To Exit For SERVICEMAN
If you have set all the parameter. Press ,
thefollowingpagewillappear:
FOR SERVICEMAN
Active the setting and exit?
CONFIRM ADJUST
NO YES
Select "YES" and press to exit the FOR
SERVICEMAN. After exiting the FOR SER-
VICEMAN,theunitwillbeturnedo󰀨.