20034064
8
GB
Technical description of the burner
4.3 Technical data
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure at test point 5) (Fig. 5) with zero pressure in the combustion chamber and maximum burner output.
(3)
Noise emission tests carried out as specified in EN 15036-1 with measurement accuracy σ = ± 1.5 dB, in the manufacturer’s com-
bustion chamber with burner operating on test boiler at maximum output.
4.4 Burner weight
The weight of the burner complete with its packaging is shown in
table.
Model RL 800/M FS2
Type 33673 X
Output
(1)
Delivery
(1)
MIN - MAX
kW
kg/h
1750/3500 ÷ 8000
147/295 ÷ 674
Fuel LIGHT OIL, viscosity at 20 °C: 6 mm
2
/s (1.5 °E - 6 cSt)
Operation Continuos
Nozzles number 1
Standard applications Boilers: water, steam, diathermic oil
Room temperature °C 0 - 50
Combustion air temperature °C max 60
Electrical supply 3N ~ 400 / 230V +/-10% 50 Hz
Electric motors rpm 2900
Fan motor
V
kW
A
380 - 415 660 - 718
21
40 - 23
Pump motor
V
kW
A
230/400
1.5
6.4/3.7
Ignition transformer
V1 - V2
I1 - I2
230 V - 2 x 5 kV
1 A - 20 A
Pump delivery (at 16,5 bar)
pressure range
fuel temperature
kg/h
bar
°C max
560
6 - 30
140
Electrical power consumption (Light oil) kW max 26
Protection level IP 54
Noise level
(3)
Sound pressure
Sound power
dB (A) 89,6
Model kg
RL 800/M 300
Fig. 1
D11082