Programmable Relay User Manual for ELC, EXM and PR Series 195 2020 v6.0 © Rievtech Co.,
Ltd. www.rievtech.com
Output Out2
Output 2 is related to the value in
the Out 2 column in the output
state table. If the value of the
angle in the angle input is higher
or the same as a value N in the
angle column in the output state
table and less than the value N+1
in the table, the value of the
corresponding Out 2 column is
copied to Out 2 (1 => output at
ON, 0 => output at OFF).
Pump Management
Description of function
Application-specific function: pumps management: (tank
management with circular pump changeover).
This function is used to set to ON a maximum of four
digital outputs which can be activated (Output 1 ... Output
4). This number is equal to the maximum number of digital
inputs (from 2 to 4) in the ON state. In addition, the
outputs set to ON are selected so that in the event of
prolonged operation, each output will have been set to
ON the same number of times.
The ON duration of the outputs is set to equal values by
applying the following technique:
As the number of ON inputs increases, the outputs
changing to ON are those following the order of the pilot
output number: 1 for Out1, 2 for Out 2, 3 for Out 3 and 4
for Out 4. For example, if the "outputs controlled"
parameter has the value 4, if pilot output number has the