Programmable Relay User Manual for ELC, EXM and PR Series 341 2020 v6.0 © Rievtech Co.,
Ltd. www.rievtech.com
CPU
6
I/O
Not Expandable
PR-6
Model: PR-6AC-R
AC
Model: PR-6DC-DA-R
DC
Item PR-6AC-R PR-6DC-DA-R
Nominal voltage AC 110V-240V
AC 85 - 265V
47-63Hz
-
-
1780VAC
34 mA (85VAC)
26 mA (265VAC)
Yes
DC 12-24V
DC 10.8-28.8V
-
Typ 5 ms
Max 0.25A
-
1.1W (10.8V DC)
1.2W (28.8V DC)
Power
Operating limits
The main
frequency range
Immunity from micro
power
Max startup current
Isolation voltage
Protection against
polarity inversions
Input No
I/O circuit diagrams
4 ( I1-I4 )
4 ( I1-I4 )
-
AC 110-240V
AC 0-40V <0.03mA
AC 79-240V >0.06mA
-
-
-
-
-
4 (I1-I4) (0..10V DC)
DC 0-28.8V
Typ 4 Hz
Contact or 3-wire PNP
Resistive
< 5V DC <0.1mA
>8V DC >0.3mA
0.4mA @ 10.8V DC
0.5mA @ 12.0V DC
1.2mA @ 24V DC
1.5mA @ 28.8V DC
0 to 1 120VACTyp. 50 ms
240VACTyp. 30 ms
1 to 0 120VACTyp. 90 ms
240VACTyp.100 ms
0 to 1Typ. 1.5 ms
1 to 0Typ. 1.5 ms
Inputs
Inputs used as digital
Inputs used as analog
Digital input
Analogue input
Input voltage
Input signal 0
Input signal 1
Response time
Sensor type
Input type
Isolation between power
supply and inputs
Isolation between inputs
Measurement range
Input impedance
Input voltage
Resolution
Cable length
Accuracy at 25
Accuracy at 55
Isolation between analog
inputs and power supply
Yes
-
-
-
-
-
-
-
DC 0-10V
28.8V DC max
9bit 0.015V
?(Max 0.03)V
?(Max 0.06)V
-
10 m max shielded & twisted
Protection against
polarity inversions
Maximum counting
frequency
Item PR-6AC-R PR-6DC-DA-R
Output No 2 (Q1-Q2)
Relay output
Resistive load 10A/Inductive load 2A
AC 250V
DC 110V
1250VA
300W
105 Operations at Rated Resistive Load
Against short-circuits: None
Against overvoltages and overloads: None
107 Operations at No Load condition
Outputs
Output type
Continuous current
Max breaking voltage
Max allowable
power force
Electrical durability
expectancy
Built-in protections
Response time OperateTime: 15 ms max ReleaseTime: 10 ms max
10Hz
2Hz
0.5Hz
Switch
frequency
Mechanism
Resistor/light load
Sensitive load
Item PR-6
Memory 64 Functional Blocks
-
10 years
Backup at 25 : 20 days,RTC accuracy: MAX ?S/day
0.6ms - 8.0ms
-
TTL interface, 1 Program/RS232 port. ModbusRTU/ASCII
only can serve as slaves
General data
Data Retentivity
Program
Backup
RTC
Cycle time
Expansion
Communication
OperationTemp -20 .. +55
-40 .. +70
IP20
48*90*64 (Unit, mm2DIN
35mm-DIN rail or screw for installation
Approx. 180g
StorageTemp
Protection
Dimensions
Installation
Weight
[Digital Input - Power DC]
(1)
DC 12-24V
+
-
[Digital Input - PowerAC]
AC 110-240V
L N I1 I2 I3 I4
(1)
DC 12-24V
max 10m
2k2/0.5W
10k max
Ca/Ta
[DC analog inputs 0-10V - Power DC ]
(1)
+
-
+
-
[Relay Outputs]
L/+
(1)
(2) (2)
Q2Q1
N/-
(1) - Fuse, circuit-breaker or circuit protector
(2) - Inductive load;

Related product manuals