CPU
6
I/O
Not Expandable
PR-6
Model: PR-6AC-R
AC
Model: PR-6DC-DA-R
DC
Item PR-6AC-R PR-6DC-DA-R
Nominal voltage AC 110V-240V
AC 85 - 265V
47-63Hz
-
-
1780VAC
34 mA (85VAC)
26 mA (265VAC)
Yes
DC 12-24V
DC 10.8-28.8V
-
Typ 5 ms
Max 0.25A
-
1.1W (10.8V DC)
1.2W (28.8V DC)
Power
Operating limits
The main
frequency range
Immunity from micro
power
Max startup current
Isolation voltage
Protection against
polarity inversions
Input No
I/O circuit diagrams
4 ( I1-I4 )
4 ( I1-I4 )
-
AC 110-240V
AC 0-40V <0.03mA
AC 79-240V >0.06mA
-
-
-
-
-
4 (I1-I4) (0..10V DC)
DC 0-28.8V
Typ: 4 Hz
Contact or 3-wire PNP
Resistive
< 5V DC <0.1mA
>8V DC >0.3mA
0.4mA @ 10.8V DC
0.5mA @ 12.0V DC
1.2mA @ 24V DC
1.5mA @ 28.8V DC
0 to 1: 120VAC:Typ. 50 ms
240VAC:Typ. 30 ms
1 to 0: 120VAC:Typ. 90 ms
240VAC:Typ.100 ms
0 to 1:Typ. 1.5 ms
1 to 0:Typ. 1.5 ms
Inputs
Inputs used as digital
Inputs used as analog
Digital input
Analogue input
Input voltage
Input signal 0
Input signal 1
Response time
Sensor type
Input type
Isolation between power
supply and inputs
Isolation between inputs
Measurement range
Input impedance
Input voltage
Resolution
Cable length
Accuracy at 25 癈
Accuracy at 55 癈
Isolation between analog
inputs and power supply
Yes
-
-
-
-
-
-
-
DC 0-10V
28.8V DC max
9bit 0.015V
?(Max 0.03)V
?(Max 0.06)V
-
10 m max shielded & twisted
Protection against
polarity inversions
Maximum counting
frequency
Item PR-6AC-R PR-6DC-DA-R
Output No 2 (Q1-Q2)
Relay output
Resistive load 10A/Inductive load 2A
AC 250V
DC 110V
1250VA
300W
105 Operations at Rated Resistive Load
Against short-circuits: None
Against overvoltages and overloads: None
107 Operations at No Load condition
Outputs
Output type
Continuous current
Max breaking voltage
Max allowable
power force
Electrical durability
expectancy
Built-in protections
Response time OperateTime: 15 ms max ReleaseTime: 10 ms max
10Hz
2Hz
0.5Hz
Switch
frequency
Mechanism
Resistor/light load
Sensitive load
Item PR-6
Memory 64 Functional Blocks
-
10 years
Backup at 25 癈: 20 days,RTC accuracy: MAX ?S/day
0.6ms - 8.0ms
-
TTL interface, 1 Program/RS232 port. ModbusRTU/ASCII
only can serve as slaves
General data
Data Retentivity
Program
Backup
RTC
Cycle time
Expansion
Communication
OperationTemp -20 癈 .. +55 癈
-40 癈 .. +70 癈
IP20
48*90*64 (Unit, mm)2DIN
35mm-DIN rail or screw for installation
Approx. 180g
StorageTemp
Protection
Dimensions
Installation
Weight
[Digital Input - Power DC]
(1)
DC 12-24V
+
-
[Digital Input - PowerAC]
AC 110-240V
L N I1 I2 I3 I4
(1)
DC 12-24V
max 10m
2k2/0.5W
10k max
Ca/Ta
[DC analog inputs 0-10V - Power DC ]
(1)
+
-
+
-
[Relay Outputs]
L/+
(1)
(2) (2)
Q2Q1
N/-
(1) - Fuse, circuit-breaker or circuit protector
(2) - Inductive load;