KBD Series Manual 33
îî”îŻîîîŻîîîŽîîîîîîŹîîîîîîîŻî¶îîîîŻîŻîîîœî¶îîî€îîîœî”îîîîîîîîîœîœîš
Locate the vent and intake air terminaîon using the
following guidelines:
1. For installaîons with mulîple Tankless Water Heaters,
refer to Figure 16 for proper exhaust and combusîon
air piping placement.
2. Roof penetraîon of the vent and intake air piping
should be such that the combusîon air intake is a
minimum 12â (30.5 cm) from the adjacent vent pipe of
the other water heater. For installaîons in the U.S.
refer to Figure 16. For installaîons in Canada, refer to
clearances required by CAN/CSA B149.1.
îłîîîîîîŻîî€îîî”îî¶îîîœî¶îîœîšîîš-îłîî¶îîîî¶îîîîœî”îî”îîîœî¶îîîîîîîîîîîîîîîî
îîîîîîîî
îîłîîîîłîîîîœîœîšîî€îîîîî¶îîî”îîîîîîîîœîî¶îî„îšî„îî€îîî”îî¶îîîœî¶îî„
Locate the vent and intake air terminaîon using the
following guidelines:
1. The total length of the vent or intake air piping must
not exceed the limits given in maximum equivalent
vent length tables. The equivalent length for 90° el-
bows and terminaîon associated with the respecîve
vent and intake air piping arrangement MUST be
subtracted from total length listed in maximum
equivalent vent length tables.
2. For roof terminaîons installed as shown in îźgure to the
right, the intake air piping must terminate using a tee
or combinaîon of elbows. The terminaîon must be
installed 12â (30.5 cm) above roof or the highest
anîcipated snow level.
3. The vent must terminate verîcally with a coupling to
facilitate the bird screen and must be located 12â (30.5
cm) minimum above the combusîon air inlet.
4. The vent and intake air terminaîons must be
located a radial distance of 12â minimum (30.5 cm)
from outer wall of vent terminaîon to outer wall of
combusîon air intake terminaîon.
îłîîîîîîŻîî€îîî”îî¶îîîœî¶îîœîšîî€îî-îłîî¶îîîî¶îîîîœî”îî”îîîœî¶îîîîîîîîîîîîîîîîîîîîîîîî
îîîîîîîî
îłîîîîîîŻîî€îîî”îî¶îîîœî¶îîœîšîîî”îŻîîîŻîîîŽîîîîîîŹîîîîîî
Cerîîźed PVC/CPVC Vent Terminaîon Opîons (conînued)
All îźgures shown in this secîon is in reference to îat roofs.
For heights of venîng passing through a pitched roof, refer
to NFPA 54/ANSI Z223.1-09 (table and îźgure 12.7.2), CSA
B149.1-10 (îźgure 8.1) Pitched Roof Terminaîon Clearances
Diagram (this manual)
î
îî€î
12â min
above air
intake
opening
12â min
12â above
grade or
anîcipated
snow level
Vent Terminaîon
Combusîon air terminaîon
12â min
above air
intake
opening
12â above
grade or
anîcipated
snow level
Vent Terminaîon
Combusîon air terminaîon
12â min
12â min
12â min
above air
intake
opening
12â above
grade or
anîcipated
snow level
Combusîon Air Terminaîon
Exhaust Vent Terminaîon
12â min