4. PROTOCOL
IMAE02-E3
28
4.3 Communication Identifier List
Communication is not possible when an identifier is specified that the AE500 can not recognize.
The number of digits for data is 6.
(Attribute RO: Read only, R/W: Read and Write)
Name
Iden-
tifier
Data range
Factory set
value
Attrib-
ute
Measured value (PV) M1 Within input range ---- RO
Alarm 1 monitor
1
AA 0: OFF 1: ON ---- RO
Alarm 2 monitor
2
AB 0: OFF 1: ON ---- RO
Alarm 3 monitor
3
AC 0: OFF 1: ON ---- RO
Alarm 4 monitor
4
AD 0: OFF 1: ON ---- RO
Burnout B1 0: OFF 1: ON ---- RO
Error code ER 0 to 255
a
---- RO
Alarm 1 setting
1
A1 Temperature
input: 0 or 0.0
R/W
Alarm 2 setting
2
A2 Voltage/current
inputs:0.0
R/W
Alarm 3 setting
3
A3 R/W
Alarm 4 setting
4
A4 R/W
Alarm 1 differential gap
setting
1
HA R/W
Alarm 2 differential gap
Setting
2
HB R/W
1
This is an identifier which enables communication at alarm 1 is provided.
2
This is an identifier which enables communication at alarm 2 is provided.
3
This is an identifier which enables communication at alarm 3 is provided.
4
This is an identifier which enables communication at alarm 4 is provided.
a
Any number other than 0 indicates errors (RAM write error, etc.) detected by the controller self-
diagnosis function. Contact your nearest RKC sales office or agent.
Continued on the next page.
Temperature input:
-1999 to +9999 °C [°F] or
-199.9 to +999.9 °C [°F]
Voltage/current inputs:
SLL (Setting limiter low limit) to
SLH (Setting limiter high limit)
Temperature
input:
2 or 2.0
Voltage/current
inputs: 2.0
Temperature input:
0 to 100 °C [°F] or
0.0 to 100.0 °C [°F]
Voltage/current inputs:
0.0 to 10.0 % of span