150 Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 5 Using 1715 Analog I/O Module Features
catalogue is updated by clicking the Scan Now button on the DTM
Catalog dialogue:
The updated DTM catalogue will contain the following 3 1715 DTMs:
The purpose and usage of the DTMs is explained in the following sections.
Enable HART Pass-Through in the Controller
The 1715 DTM uses HART Pass-Through to communicate with HART devices.
Before it can do this, HART Pass-Through must be enabled for the 1715, and
HART enabled on the channels that HART devices are connected to.
To enable HART Pass-Through, do the following:
1. Open the RSLogix application containing the 1715 Adapter and its
I/O modules.
2. Enable HART on the I/O modules and channels to which you wish to
perform Pass-Through requests, see previous section on how to do this.
3. Enable HART Pass-Through for the 1715 by setting the output tag
<AENTR>:O.HARTPassThrough:
4. Compile and download the application.
Using Factory Talk Asset Center with Analog Modules
In order to use the DTMs, a DTM network must first be configured in the asset
management system.
Using the Rockwell AssetCentre, for example, do the following:
1. Make sure the DTM catalogue is up to date, see previous section on how
to do this.