Rockwell Automation Publication 1715-UM001J-EN-P - December 2020 151
Chapter 5 Using 1715 Analog I/O Module Features
2. Right click on the Host PC icon at the top of the tree, click Add DTM.
Select a ’1715 EtherNet/IP Gateway DTM’, click OK.
3. Right click on the ’1715 EtherNet/IP Gateway DTM’ that has just been
added, click Add DTM. Select a 1715-IF16 or 1715-OF8I, depending on the
type of physical I/O module present. Repeat for each I/O module.
4. Now add the HART device DTM’s. Right click on an I/O module, select
Add DTM. Select the device DTM, then select the I/O channel to which
the device is connected. Note that the first I/O channel number is 0.
5. The 1715 I/O DTMs must also be configured as described below. This can
be done before or after adding the device DTMs.
1715-DTM Configuration
1715 EtherNet/IP Gateway DTM
This DTM does not require configuration.
IMPORTANT
Device DTMs are provided by the device manufacturer, and
require separate installation, not covered in this guide.