EasyManua.ls Logo

Rockwell Automation Allen-Bradley 1715-OB8DE - Appendix E 1715-AENTR Adapter

Rockwell Automation Allen-Bradley 1715-OB8DE
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020 279
Appendix F
I/O Tag Definitions
1715-AENTR Adapter This section describes the tags that are associated with the 1715-AENTR
adapter.
Table 63 - Input
Tag Name Data Type Definition
Fault DINT, Binary
Adapter fault bit: 0 when at least one adapter is present and reporting valid data, OxFFF_FFFF when no
adapters are present, no Logix connection exits, or reported data is invalid.
Status
DINT, bit field
Adapter redundancy and power status:
Bit 0: ModAFault 0 = good
1 = fault or module not present
Bit 1: ModBFault 0 = good
1 = fault or module not present
Bit 8: Power1Fault 0 = good
1 = fault or module not present
Bit 9: Power2Fault 0 = good
1 = fault or module not present
LinkStatus DINT, bit-field
Adapter Ethernet port status:
Bit 0: PortA1Connected 0= Inactive
1 = Active
Bit 2: PortA2Connected 0= Inactive
1 = Active
Bit 3: PortB1Connected 0= Inactive
1 = Active
Bit 4: PortB2Connected 0= Inactive
1 = Active
FullDuplex DINT, bit-field Adapter Ethernet port half/full duplex status:
Bit 0: PortA1FullDuplex 0= Inactive
1 = Active
Bit 2: PortA2Duplex 0= Inactive
1 = Active
Bit 3: PortB1Duplex 0= Inactive
1 = Active
Bit 4: PortB2Duplex 0= Inactive
1 = Active
PortA1ANSTatus SINT, enumerated Enumerated adapter Ethernet port auto-negotiation status:
Value Description
0 Auto-negotiation in progress
1
Auto-negotiation of duplex and speed detection failed; by using a default
value for speed and duplex
2
Auto-negotiation of duplex but detected speed; by using a default value for
duplex
3 Successfully negotiated duplex and speed
4 Auto-negotiation not attempted, by using forced speed and duplex values

Table of Contents