Rockwell Automation Publication 1794-UM061B-EN-P - March 2020 17
1794 FLEX I/O Diagnostic Digital Modules Overview Chapter 1
Capabilities of the 1794-IB16D include:
61131-2 Type 3 compatible sinking inputs.
interface with PNP sourcing sensors.
10…31.2V DC operating range.
provides up to 50 mA to power an attached sensor.
detects for an open wire condition down to 50 A.
You need a dummy resistor to mask the channel diagnostic function for each
unused sensor port. Used sensor ports must have a 50 A minimum current draw
with the input field device in both the on- and off-state.
1794-OB16D Diagnostic Output Module Compatibility
You can use FLEX I/O diagnostic output modules to drive various output
devices. Typical output devices include the following.
•Relays
Solenoids
•Contactors
•Indicators
Small motor starters
When you design a system using FLEX I/O diagnostic output modules, you must
consider:
The output must supply the necessary surge and continuous current for the
output device being used.
When sizing output loads, check the documentation that is supplied with
the output device for the surge and continuous current needed to operate
the device.
Capabilities of the 1794-OB16D diagnostic output module include:
sourcing style outputs for loads that are connected to common.
10…31.2V DC operating range.
provides continuous current of 0.5 A maximum (8 A per module),
2.0 mA minimum per output.
capable of 2 A surge for 50 ms, repeatable every 2 s.
protection from short circuit and overload.
You need a dummy resistor to mask the channel diagnostic function for each
unused output channel.