EasyManua.ls Logo

Rockwell Automation Allen-Bradley 1794-IB16D - Chapter 3: FLEX I;O Diagnostic Output Module; About the 1794-OB16 D Diagnostic Output Module

Rockwell Automation Allen-Bradley 1794-IB16D
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1794-UM061B-EN-P - March 2020 29
Chapter
3
About the FLEX I/O Diagnostic Output Module
Introduction
In this chapter, you will learn about the diagnostic output module, cat. no.
1794-OB16D.
About the 1794-OB16D
Diagnostic Output Module
The 1794-OB16D diagnostic output module provides 16 24V DC sourcing
outputs with open-wire, short-circuit, and user supply reverse polarity diagnostic
features. The module monitors current and voltage at each output channel.
The module detects:
an open fault if no current is present at the output terminal.
a short fault if no voltage is present at the output terminal.
a reverse-polarity fault if reverse voltage is applied.
When an open or short fault is detected:
the corresponding channels red indicator is illuminated.
the module’s red fault indicator is illuminated.
the module’s open or short error bit is set.
the module error bit is set.
When a user supply reverse-polarity fault is detected:
the modules red fault indicator is turned on,
and the reverse error bit is set.
the module error bit is set.
For Information About See Page
About the 1794-OB16D Diagnostic Output Module 29
Diagnostic Fault Detection 31
Module Protection Functions 32
Module Limitations 34
Configure Your Output Diagnostic Module 34

Table of Contents