30 Rockwell Automation Publication 1794-UM061B-EN-P - March 2020
Chapter 3 About the FLEX I/O Diagnostic Output Module
Wiring Output Loads
You can use the 1794-OB16D diagnostic module with the 1794-TB2, 1794-TB3,
or 1794-TB3S terminal base units.
User power can be wired to the (+) voltage and common terminals directly, or
power can be daisy chained from the FLEX I/O terminal base units on the DIN
rail. Output channels are not isolated from one another. All 16 channels share a
common return (group isolation from FLEX I/O system-side logic voltages).
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Output Channel 0-15
Common
(1794-TB3 shown)
-V
Voltage
In +V
Voltage
Out +V
Voltage (24V dc)
Terminals 35 thru 50 not available on 1794-TB2
A
B
C
Common
-V
Common
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FLEX TB2/3/3S
Terminal Base
A0-A15
B17-B32
C34
B16
Output
Common
V+
V-
Output
Device
24V DC
External User
Power Supply