EasyManua.ls Logo

Rockwell Automation Allen-Bradley 1794-IB16D - Tally Memory Requirements

Rockwell Automation Allen-Bradley 1794-IB16D
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56 Rockwell Automation Publication 1794-UM061B-EN-P - March 2020
Chapter 5 Configure FLEX I/O Digital Modules on a DeviceNet Network
Tally Memory
Requirements
The 1794-ADN FLEX I/O adapter packs the data of its I/O modules into a
contiguous block of input or output bytes. By default, the modules share DINT
elements in the scanner.
For example, to determine the amount of scanner memory that is required for
your adapter and its I/O modules
As an option, give each module its own memory location (DINTs) within the
scanner. This may make your programming easier. Assign one address for the
1794-ADN and all modules that you connect to it.
Device Input Size of
Device
(bytes)
Output Size
of Device
(bytes)
FLEX I/O adapter—1794-ADN 2 0
digital output module—1794-OB16D 2 2
digital input module—1794-IB16D 2 0
Total 6 2
Device Address Input Size of
Device
(bytes)
Input Memory
in Scanner
(DINTs)
Output Size
of Device
(bytes)
Output Memory
in Scanner
(DINTs)
Start/stop Buttons 1 1 1 1
Motor Starter 4 1 4 1
FLEX I/O Adapter w/modules 6 2 2 1
Total
1. Add the input bytes of each module + 2 bytes for the adapter.
2. Add the output bytes of each module (0 for
the adapter).
3. Add the totals to the main tally.