Publication 900-UM007D-EN-E - January 2011
3-60 Configuration & Basic Operation
Heater Overcurrent Alarm
Set-up
To activate the heater overcurrent alarm (HOA), set the:
1. Heater Overcurrent Use parameter to ON in the Advanced Setting
function group and
2. Heater Overcurrent Detection 1 and Heater Overcurrent Detection 2
parameters in the Adjustment function group.
Note: This procedure configures the Heater Overcurrent Detection 1
parameter to 20.0.
Moving to the Advanced Setting Function Group
The default setting for the Heater Overcurrent Use parameter is ON, so set
the Heater Overcurrent Detection 1 parameter
Move to the Advanced Setting function group. Press the O Key for at least three seconds to
move from the Operation to the Initial Setting function group.
Figure 3.125
3. Press the M Key to select the Move to Advanced Setting function
group parameter. (For details on moving between function groups, refer
to 4-8 Moving to the Advanced Setting function group.)
Figure 3.126
4. Press the D Key to enter the password (-169), and move from the
Initial Setting function group to the Advanced Setting function group.
Figure 3.127
The top parameter in the Advanced Setting function group is displayed.
init
off
Move to the
Advanced
Setting
function group