154 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 9 Parameter Descriptions
Selects the drive status that will energize user-configurable digital output 1.
See AC Line I/O Board Description (Frame 3 Only)
on page 25 through
Combined I/O Board Description (Frame 4 Only)
on page 29 for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
For Frame 3 drives (firmware version 1.x), most of the values possible for this
parameter only affect the operation of the drive if an optional Standard I/O
board is present.
The only exception is when Dig Out1 Sel (380) is set to Aux Run (28). If the
parameter is set to Aux Run (28), digital output 2 on the AC Line I/O board is
energized whenever the inverter is running, even if an optional Standard I/O
board is not present.
380
Digital Out1 Sel
Range: 1 = Fault (De-energized = Fault, Energized = No Fault)
2 = Alarm (De-energized = Inverter Alarm, Energized = No Inverter Alarm)
3 = Ready
4 = Run
5 = Forward Run
6 = Reverse Run
7 = Auto Restart
8 = Powerup Run
9 = At Speed
10 = At Freq
11 = At Current
12 = At Torque
13 = At Temp
14 = At Bus Volts
15 = At PI Error
16 = DC Braking
17 = Curr Limit
18 = Economize
19 = Motor Overld
20 = Power Loss
21 = Input 1 Link
22 = Input 2 Link
23 = Input 3 Link
24 = Input 4 Link
25 = Input 5 Link
26 = Input 6 Link
27 = Shunt Trip
28 = Aux Run
Default: 27 = Shunt Trip
Access: 0 Path: Inputs & Outputs > Digital Outputs
See also: 1...4, 12, 48, 53, 137, 147, 157, 184, 218, 381...383, 385, 386
381
Dig Out1 Level
Range: 0.0...819.2 [0.1]
Default: 0.0
Access: 0 Path: Inputs & Outputs > Digital Outputs
See also: 380