Rockwell Automation Publication 750-IN119A-EN-P - April 2022 63
Chapter 5 Power Wiring
Power Cable Specifications Various cable types are acceptable for drive installations. For an in-depth
discussion of cable types, including a table of maximum motor cable lengths,
refer to the Wiring and Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives, publication DRIVES-IN001
.
Power Cable Types Acceptable for 400…480 Volt Installations
ATTENTION: National codes and standards (NEC, BSI, and so forth) and local
codes outline provisions for safely installing electrical equipment. Installation
must comply with specifications regarding wire types, conductor sizes,
branch circuit protection, and disconnect devices. Failure to do so can result
in personal injury and/or equipment damage.
Table 6 - Power Cable Recommendations
Type Cable Description
Minimum Insulation
Rating
Input Power
(1)(2)
(1) Signal wires should be separated from power wires by at least 0.3 meters (1 foot).
(2) The use of shielded wire for AC input power may not be necessary but is always recommended.
Standard
All frame sizes:
Three tinned copper conductors with XLPE
insulation.
Copper braid/aluminum foil combination shield and
tinned copper drain wire, three drain wires per
cable assembly.
PVC jacket.
600V,
75 °C (167 °F)
(3)
(3) The minimum insulation rating for input power wire must be at least equal to the nominal system voltage rating.