Setting motor torque during position recovery
Adjust motor torque with parameter  if, during position recovery, the values set with parameters  and  are insuf-
ܪHNJSYYTFQQT\YMJLFYJYTHTRUQJYJYMJRFSTJZ[WJ
If position recovery is not completed, normal gate operation will not be resumed.

The response of the obstacle detection system depends solely on the values set for parameters  and .

The response of the obstacle detection system depends on the values set for parameters  and  and on the maxi-
mum current value stored during travel acquisition.

The response of the obstacle detection system is a 70% reduction in maximum torque for a period of 1 s.

The response of the obstacle detection system is a 80% reduction in maximum torque for a period of 2 s.

The response of the obstacle detection system is a 100% reduction in maximum torque for a period of 3 s.

The response of the obstacle detection system is a 100% reduction in maximum torque for a period of 5 s.

Setting opening and closing speed
N.B.: YMJXUJJIXJYYNSLWFSLJKTWYMJXUJHNܪHRTYTWNSXYFQQJINXFZYTRFYNHFQQ^XZGIN[NIJINSYTJVZFQXJLRJSYX

See chapters 14 and 15

01= 6 m/min ... 10= maximum speed.
 
Setting end of manoeuvre constant approach speed
Once deceleration is complete, the gate continues to the limit switch at constant speed. The distance is set with the
parameters  and .

01= 2 m/min; 02= 2,5 m/min; 03= 3 m/min; 04= 3,5 m/min; 05= 4 m/min.

Setting number of automatic closure attempts after activation of sensing edge
or obstacle detection (crush protection)

No automatic closure attempts.

From 1 to 3 automatic closure attempts.
We recommend setting a value equal to or lower than the value set for parameter $.
Automatic closure is only performed if the gate is completely open.

Setting photocell mode during gate opening (FT1)

DISABLED. Photocell is not active or not installed.

STOP. The gate stops and remains stationary until the next command is received.

IMMEDIATE REVERSE. The gate reverses immediately if the photocell is activated during gate opening.

TEMPORARY STOP. The gate stops as long as the photocell is obstructed. The gate resumed opening when the photocell
is cleared.

DELAYED REVERSE. The gate stops if the photocell is obstructed. The gate closes when the photocell is cleared.

Setting photocell mode during gate closing (FT1)

DISABLED. Photocell is not active or not installed.

STOP. The gate stops and remains stationary until the next command is received.

IMMEDIATE REVERSE. The gate reverses immediately if the photocell is activated during gate closure.

TEMPORARY STOP. The gate stops as long as the photocell is obstructed. The gate resumed closing when the photocell
is cleared.

DELAYED REVERSE. The gate stops if the photocell is obstructed. The gate opens when the photocell is cleared.

Photocell (FT1) mode with gate closed
This parameter is not visible if $ , $  or $  is set.

If the photocell is obstructed, the gate cannot open.

The gate opens when an open command is received, even if the photocell is obstructed.

The photocell sends the gate open command when obstructed.