Protocol analysis
R&S
®
RTE
601User Manual 1326.1032.02 ─ 20
Figure 13-31: Structure of a byte field
Data bytes are transmitted LSB first.
The identifier byte consists of 6 bits for the frame identifier and two parity bits. This
combination is known as protected identifier.
Trigger
The R&S RTE can trigger on various parts of LIN frames. The data line must be con-
nected to an input channel, triggering on math and reference waveforms is not possi-
ble.
You can trigger on:
Frame start (synchronization field)
Specific identifier or identifier range
Data pattern in the message
Wake up signal
Checksum error (error in data), parity error (error in identifier)
13.6.2 LIN configuration
13.6.2.1 LIN configuration settings
Access: [PROTOCOL] > "Decode" tab > "Protocol" = LIN
Make sure that the tab of the correct serial bus is selected.
LIN (option R&S RTE-K3)